Fire Code Violations by School - WKRN News 2

Fire Code Violations by School

Updated:

ACADEMY OLD COCKRILL
2009: Not open yet
2010/11:
1. Service emergency lights in the stairwell by #111, across from #111 & 110, outside the auditorium and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Classroom (and egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
3. Seal penetrations in the corridor next to Rm #7 and outside the auditorium.  NFPA 101: 8.3.5.1*
4. There shall be no storage in stairwells. Remove shredder containers.  NFPA 101:  7.2.2.5.3*
5. Replace center "bar" of the cafeteria doors.  This is part of the fire-rated door assembly.  NFPA 101: 8.2.2.5
11/12:
1. Classrooms shall have one window free and clear for rescue.  NFPA 101: 15.2.11.1.1
2. Seal penetrations in the upper level corridor.  NFPA 101: 8.3.5.1*
3. Relocated fire extinguisher so that it is easily accessible.  NFPA 10: 1.5.3

ACADEMY OPRY MILLS
2009: N/A
2010/11: NONE
2011/12: N/A

ALEX GREEN
2009:
1. Service exit sign by #124.  NFPA 101: 7.10.9.1
2. Service emergency lights on the opposite side of the emergency light by #127.  Periodic testing is required.  NFPA 101: 7.9.3
2010/11:
1. Service fire extinguisher in the closet next to the teacher workroom by #153.  NFPA 10: 6.3.1
2. Relocate smoke detector so that it is not closer than 3 ft. to an air diffuser.  NFPA 72: 5.7.4.1
2011/12:
1. Service emergency lights in the foyer near 2nd grade and cafeteria.  NFPA 101: 7.9.3
2. There shall be no storage in the boiler room. Remove desks and chairs.  IFC 315.2.3
3. Kitchen hood filters shall be installed properly.  NFPA 96: 6.2.5

AMQUI ELEMENTARY
2009: NONE
2010/11: NONE
2011/12:
1. Service emergency lights next to #135, 136, in the cafeteria near exit and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3

ANDREW JACKSON
2009: NONE
2010/11: preschool only
2011/12: NONE

ANTIOCH HIGH
2009:
1. Relocate the smoke detector by D11 fire doors so that it is not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
2. The use of open flame candles is prohibited within the building.  NFPA 1: 10.1.5
2010/11:
1. Service emergency lights throughout the auditorium.  NFPA 101: 7.9.3
2. Fire doors in gym area shall not be propped open. (Repair power to the magnetic hold devices or keep doors closed.)  NFPA 101: 7.2.1.8.1*
3. Dryer vent shall be vented to the outside (in training room). NFPA 211: 10.7.3.3
2011/12:
1. Replace ceiling tile in dance room (#104).  NFPA 101: 8.4.2

ANTIOCH MIDDLE
2009:
1. Service or repair emergency lights in both gyms, on the stage and in the rear of kitchen.  Periodic testing is required.   NFPA 101: 7.9.3
2. Classrooms (Rooms #108, 110, 112, 127, 135, 137) shall have not less than one outside window that remains clear, unobstructed, and operable for emergency rescue at all times.   NFPA 101: 15.2.11.1
2010/11:
1 Service emergency lights next to #222 and stairwell across from #112.  NFPA 101: 7.9.3
20111/12:
1. Fire alarm panel shows "loop" trouble on one panel and normal on other.  Repair immediately.   NFPA 101: 4.6.12.1
2. Service and tag fire extinguisher in gym (main building side).  NFPA 10: 6.3.1 and NFPA 10: 6.3.4
3. Service emergency lights in gym, by room #201, 206, 226, 127 as needed.  NFPA 101: 7.9.2.3*

APOLLO MIDDLE
2009:
1. Service emergency lights in the auditorium on door #123 side, outside the auditorium across from the kitchen, in the upper level stairwell across from #215 and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Classroom (and egress corridor) doors shall not be propped open.  There were several propped throughout.  Remove door stoppers.  NFPA 101: 7.2.1.8.1*
3. Classrooms shall have one window for rescue or an adjacent door between classrooms that allow access to an exit including #209 and 111, 112, and 116 that have windows that open into the closed in courtyard.  NFPA 101:15.2.11.1.1 and 15.2.11.1.2
*Remember, there is an additional fire drill required within the first 30 days.
2010/11:
1. Fire alarm panel in trouble mode. Repair immediately.  NFPA 101: 4.6.12.1
2. Service (and provide) emergency lights for the gym and locker rooms.  Periodic testing is required.  NFPA 101: 7.9.3
3. Classroom (and egress corridor) doors shall not be propped open (#207, 204, and 103).  Repair stairwell door next to #105.  NFPA 101: 7.2.1.8.1*
4. Seal penetrations in the corridor next to Rm #7 and outside the auditorium.  NFPA 101: 8.3.5.1*
5. Classrooms (#111, 112, 113A & B) with rescue windows leading into courtyard shall have access to a 2nd exit. The door from the courtyard leading into the building shall be unlocked for use during normal operating hours.  NFPA 101: 15.2.11.1.1
2011/12:
1. Kitchen suppression system shall be serviced every six (6) months.  NFPA 96: 11.2.1
2. Repair exit sign in the large gym.  NFPA 101: 7.10.9.1
2. Classroom (and egress corridor) doors shall not be propped open including rooms# 215, 214, 216, 218, and library.  (non-sprinklered areas)  NFPA 101: 7.2.1.8.1*
3. Classrooms shall have one window free and clear for rescue (rooms# 210, 209, and 111, 112 where windows are in closed in area in center of building).  NFPA 101: 15.2.11.1.1

AZ KELLY ELEMENTARY
2009: NONE
2010/11: NONE
11/12: NONE

BAILEY MIDDLE
2009:
1. Service emergency light by the elevator room next to the gym.  Periodic testing is required.  NFPA 101: 7.9.3
2. Seal penetrations near Room#101.  NFPA 101: 8.3.5.1*
3. Replace ceiling tile missing in stairwell #2.  NFPA 101: 8.3.4.1
2010/11:
1. Service fire extinguisher next to #224.  NFPA 10: 6.3.1
2. Service emergency lights across from kitchen, in stairwell by #321.  NFPA 101: 7.9.3
3. Seal penetration in stairwell (and other side into class) by #25.  NFPA 101: 8.4.4.1
2011/12:
1. Service emergency lights in stairwell, gym and locker rooms, boiler room, auditorium stage and across from main office, by #301, 307, in stairs #3 (3rd floor) and throughout.  NFPA 101: 7.9.2.3*
2. Service fire extinguisher by room #300, and throughout including class K.  NFPA 10: 6.3.1
3. Seal penetrations in corridor by #304.  NFPA 101: 8.4.4.1
4. Replace missing ceiling tile in stair #1 (3rd floor).  NFPA 101: 8.4.2

BELLEVUE MIDDLE
2009:
1. The fire alarm system shows a trouble signal on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Classrooms shall have one window for rescue (P520).  NFPA 101: 15.2.11.1.1
3. Service emergency lights throughout.  Periodic testing is required.  NFPA 101: 7.9.3
4. Provide emergency lighting for the library.  NFPA 101: 7.9.1.1
5. De-clutter the custodial hall.  Surplus supply is excessive and does not allow for corridor width to be properly maintained.  Also corridors shall not be used for storage.  NFPA 1: 10.1.1 and 7.3.4.1
6. Classroom and egress corridor doors shall not be propped (including the Guidance and Main front offices).  NFPA 101: 7.2.1.8.1*
2010/11:
1. Service emergency lights in the library hall, kitchen, stairwell to lower level, by #92 and throughout.  Periodic testing is required.  NFPA 101: 7.9.3
2. Seal penetrations in the custodian closet by the boys restroom next to the library.  NFPA 101: 8.3.5.1*
3. Classroom (and egress corridor) doors shall not be propped open.  Remove door stoppers.  NFPA 101: 7.2.1.8.1*
4. Corridors shall not be blocked with excess desks and storage (by #301).  NFPA 1: 10.1.1 and 7.3.4.1
2011/12:
1. There shall be one window for emergency rescue (Portable nearest exit by elevator).  NFPA 101: 15.2.11.1.1
2. Seal penetrations in the boiler room.  NFPA 101: 8.3.5.1*
3. Classroom (& egress corridor) doors shall not be propped open unless all classrooms have a door directly to the outside (including library).   NFPA 101: 7.2.1.8.1*
4. There shall be no storage in the boiler room.  Remove chairs and desks.  IFC 315.2.3
5. Service emergency lights in the library, auditorium, room #300 and stairwell, and by room #89.  NFPA 101: 7.9.3

BELLSHIRE ELEMENTARY
2009:
1. Classroom and egress corridor doors shall not be propped.  NFPA 101: 7.2.1.8.2
2. Replace ceiling tile throughout the POD including custodial closet.  NFPA 101: 8.3.4.1
2010/11:
1. Classroom (& egress corridor) doors shall not be propped open.  Remove door stoppers.  NFPA 101: 7.2.1.8.1*
11/12: NONE

BORDEAUX ENHANCED ELEMENTARY
2009:
1. Service exit signs in front of the upper and lower level elevator near the cafeteria and by #205.  NFPA 101: 7.10.9.1
2. Relocate smoke detectors (two in the gym) so that they are not located in a direct airflow nor closer than 3 ft. where airflow prevents operation of the detectors.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
3. Classroom (and egress corridor) doors shall not be left in the open position (Rooms #112, 130, 131, 133, 138, 140, 224).  Provide door closers as needed.   NFPA 101: 7.2.12.3.4.3
2010/11:
1. Classroom (and egress corridor) doors shall not be propped open (throughout bldg).  NFPA 101: 7.2.1.8.1*
2. There shall be no storage in stairwells (lower level across from room#201).  NFPA 101: 7.2.2.5.3*
3. Fire doors by room #104 shall not be propped open and also doors by courtyard exit (repair magnetic door holders).  NFPA 101: 7.2.1.8.1*
4. Seal penetrations in boiler room and stairwell outside cafeteria.  NFPA 101: 8.4.4.1
2011/12:
1. Service exit sign by room #192 (Fentress).  NFPA 101: 7.10.9.1

BRICK CHURCH MIDDLE
2009:
1. Service emergency lights by Rooms#187 & 189 and at the computer room.  Periodic testing is required.  NFPA 101: 7.9.3
2010/11:
1. Service emergency lights outside computer room, boiler room and by exit near chorus room.  NFPA 101: 7.9.3
2. Replace missing ceiling tile in library.  NFPA 101: 8.4.2
2011/12:
1. Service and tag fire extinguisher in room #192.  NFPA 10: 6.3.1
2. Sprinkler room shall have spare (6) sprinkler heads in spare box.  NFPA 101: 13:6.2.9

BROOKEMEADE ELEMENTARY
2009: Daycare only
2010/11: Vacant building
11/12: Vacant building

BUENA VISTA ELEMENTARY
2009:
1. Stairwell door (by #109) shall not be propped open.  NFPA 101: 7.2.1.8.1*
2. Service fire extinguisher across from the Playroom.  NFPA 10: 6.3.1
3. Artwork shall not cover more than 50% of walls (Kindergarten hall in are of #124) NFPA 101: 15.7.4.3
2010/11: NONE
2011/12:
1 Sprinkler system shall be serviced annually. (Last tag 2009)   NFPA 25: 5.2.1.1

CALDWELL ELEMENTARY
2009:
1. Seal penetrations in electrical room#012 (under stair).  NFPA 101: 8.3.5.6.1
2010/11: NONE
2011/12: NONE

CAMERON MIDDLE
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service emergency lights by #108 and in the lower level stair by the Alumni room.  Periodic testing is required.  NFPA 101: 7.9.3
3. Seal penetrations in the stairwell by Alumni room, above the elevator door-corridor side, in the basement electrical room by the cafeteria, and in the stairwell by the basement teachers lounge.  NFPA 101: 8.3.5.1*
2010/11:
1. Seal penetrations inside and outside stairwell by boiler room.  NFPA 101: 8.4.4.1
2. Service emergency light in kitchen.  NFPA 101: 7.9.3
2011/12:
1. Service or replace emergency lights in the small gym and throughout.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service or repair exit signs by the cafeteria and in the large gym.  NFPA 101: 7.10.9.1
3. Replace ceiling tile in the small gym and throughout various areas of the building.  NFPA 101: 8.4.2
4. Replace missing extinguishers throughout bldg.  NFPA 10: 1.5.7
5. Maintain 6 feet corridor width throughout.  Remove clutter n the brick hallway behind the gym.  NFPA 101: 15.2.3.2

CANE RIDGE HIGH SCHOOL
2009:
1. Service fire extinguisher across from the auditorium by the restrooms, by the lower level elevator lobby,  by the old weight room and in the gym.  NFPA 10: 6.3.1
2. There shall be no storage in stairwells (next to the old weight room).  NFPA 101: 7.2.2.5.3*
3. Service kitchen suppression system every 6 months.  NFPA 96: 11.2.1
2010/11:
1 Service Class K fire extinguisher in the kitchen.  NFPA 10: 6.3.1
2 Laundry room dryer shall be vented to the outside.  NFPA 211: 10.7.3.3
3 Remove excess desks and other items from corridor (by receiving) to maintain 6 ft. width.  This area shall not be used for storage.  NFPA 101: 14.2.3.2
4 Replace missing fire extinguisher outside gym lobby.  Also, arrange equipment in weight room so that the fire extinguisher is not blocked.  NFPA 10: 1.5.3
5 Arrange equipment in weight room so that the exit is not blocked.  NFPA 101: 7.1.10.1*
2011/12: NONE

CARTER LAWRENCE
2009: NONE
2010/11: NONE
2011/12: NONE

CHADWELL ELEMENTARY
2009:
1. Extension cords shall not be used in place of permanent wiring (room #40).  NFPA 1: 11.1.5
2. Good housekeeping shall be maintained.  Remove overflow of paper, material, storage, and other combustibles so that the fire load is not excessive.   NFPA 101: 4.6.1.2 
2010/11: Moved to Knight Road
2011/12:
1. Classroom (& egress corridor) doors shall not be propped open. (#208).  NFPA 101: 7.2.1.8.1*
2. There shall be one window free and clear for rescue.  (Portable 309)  NFPA 101: 15.2.11.1.1

CHARLOTTE PARK
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service emergency lights throughout the gym and by Rooms# 2 and 8.  Periodic testing is required. NFPA 101: 7.9.3
3. Smoke detector in the boiler room shall not be covered with tape.  Fire-warning equipment shall be maintained so that it functions properly.  NFPA 72: 11.10
2010/11:
1. Seal penetrations above conference room across from #213, #14 and throughout.  NFPA 101: 8.4.4.1
2. Repair emergency light by #5 & by #15 and service emergency light in kitchen.  NFPA 101: 7.9.3
3. Classrooms shall have one window free and clear for rescue.  (Fun Company Portable).  NFPA 101: 15.2.11.1.1
2011/12:
1. Service emergency lights in the pod and in the right hall near library.  NFPA 101: 7.9.3
2. Seal penetrations around room #8.  NFPA 101: 8.4.4.1

CHURCHWELL MUSEUM
2009: N/A
2010/11: N/A
2011/12:
1. Artwork & teaching materials shall not cover more than 50% of walls. (1st grade hall)  NFPA 101: 15.7.4.3
2. Sprinkler system shall be serviced annually.  NFPA 25: 5.2.1.3
3. There shall be a wrench in sprinkler room.  NFPA 13: 6.2.9.6

COCKRILL ELEMENTARY
2009:
1. Service emergency lights throughout the gym.  Periodic testing is required.  NFPA 101: 7.9.3
2. The exit door by the rear mechanical room shall be repaired to open with reasonable force.   NFPA 101: 7.2.1.4
2010/11: NONE
2011/12: NONE

COHN ALTERNATIVE
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Seal penetrations in the custodian office, in the custodian closet near their office and outside of 305-A.  NFPA 101: 8.3.5.1*
3. Classroom (and egress corridor) doors shall not be propped open.  Remove door stoppers.  Stairwell doors shall not be propped either.  NFPA 101: 7.2.1.8.1*
4. Classrooms (2nd floor) shall have one window for rescue. (different floor than last school year)  NFPA 101: 15.2.11.1.1
2010/11:
1.Classroom (and egress corridor) doors shall not be propped open.  Remove door stoppers.  NFPA 101: 7.2.1.8.1*
3 Classrooms (2nd floor) shall have one window for rescue.  NFPA 101: 15.2.11.1.1
1 Service emergency lights outside #211A, next to #207 and in the gym.  Periodic testing is required.  NFPA 101: 7.9.3
2 Service exit signs in the gym.  NFPA 101: 7.10.9.1
11/12:
1. Fire alarm panel in trouble. Repair immediately.  NFPA 72: 10.2.1.2
2. Replace the missing fire extinguisher in the hallway between the two gyms.  NFPA 10: 6.1.3
Repeated violations:
3. Classroom (and egress corridor) doors shall not be propped open.  Remove door stoppers.  NFPA 101: 7.2.1.8.1*
4. Classrooms (#201, 203, 205, 206, 209, 215, 217, 312) shall be equipped with one window for rescue.  NFPA 101: 15.2.11.1.1
5. Service emergency lights outside #211A, next to #207, by stair next to #312, in stair by #302, in the gym and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
6. Service exit signs in the gym.  NFPA 101: 7.10.9.1

COLE ELEMENTARY
2009:
1. Service emergency lights in gym by the playground exit and above fire doors by Speech room.  Periodic testing is required.   NFPA 101: 7.9.3
2. Classrooms (P03, P05, P10) shall have not less than one outside window that remains clear, unobstructed, and operable for emergency rescue at all times.   NFPA 101: 15.2.11.1
3. Seal penetrations inside door of janitors closet near#204 and above fire doors by Speech room.  NFPA 101: 8.3.4.1
4. Service exit sign outside boiler room.  NFPA 101: 7.10.9.1
5. Fire drills shall be conducted monthly and be documented.  NFPA 101: 15.7.2.1
6. Grease filters shall be installed at an angle not less than 45 degrees from the horizontal.  NFPA 96: 6.2.3.5  
2010/11:
1. Fire alarm panel in trouble mode.  Repair immediately.  4.6.12.1
2. Sprinkler system shall be serviced annually.  NFPA 25: 5.2.1.1
3. Seal penetration in the boiler room.  NFPA 101: 8.3.5.1*
4. Classroom (& egress corridor) doors shall not be propped open. Remove wedges and door stoppers. (non-sprinklered areas)  Also, repair room#310 door so that it does not "stick" on the floor (in the open position).  NFPA 101: 7.2.1.8.1*
2011/12:
1. Service emergency lights by the ramp to 2nd & 3rd grade, across from room #105 and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Extension cords shall not be used in place of permanent wiring.  IFC 605.5
3. Classrooms shall have one window free and clear for rescue (P04).  NFPA 101: 15.2.11.1.1
4. Provide a door closer for Conference room next to #202.  NFPA 101: 7.2.1.8

CORA HOWE
2009:
1. Classrooms shall have one window free & clear for rescue (Computer lab).  NFPA 101: 15.2.11.1
2. Service exit sign inside & outside the stairwell to the cafeteria, in the end class in Cluster #2,in the conference area of Cluster#3 and near Rm#21.  NFPA 101: 7.10.9.1
3. There shall be no storage in stairwells.  Remove chairs under stairs.  NFPA 101: 7.2.2.5.3
4. Emergency egress drills shall be conducted monthly.  Provide documentation.  NFPA 101: 15.7.2.2
2010/11:
1 Fire alarm panel in trouble mode.  Repair immediately.  NFPA 101: 4.6.12.1
2 Service emergency lights by the lower level elevator, by Art class, and by Rm #12.  Periodic testing is required.  NFPA 101: 7.9.3
3 Smoke detectors shall not be located within 3ft. of an air diffuser (at the entrance to Cluster#2).  NFPA 72: 5.7.4.1
4 Repair the custodian clooset door across from the computer lab so that it closes.  NFPA 101: 7.2.1.8.1*
5 Seal penetrations in the stair outside the boiler room.  NFPA 101: 8.3.5.1*
2011/12: NONE

CRIEVE HALL
2009:
1. Service emergency lights in all Portable classrooms, by the janitor's closet#116 and outside the cafeteria.  Periodic testing is required.  NFPA 101: 7.9.3
2. Classrooms shall have one window free and clear for rescue.  NFPA 101: 15.2.11.1.1
3. Seal large hole behind clock in library.  NFPA 101: 8.3.5.1*
2010/11: NONE
2011/12:
1. Seal penetrations in janitors closet across from #119A.  NFPA 101: 8.3.4.
2. Stairwell door shall not be propped open (B #004).  Repair magnetic hold open device or keep door closed.  NFPA 101: 7.2.1.8.1* 

CROFT MIDDLE
2009:
1. Service emergency lights by the upper level stair#2, by #316, 254, 326 & 333, in girls restroom by #326 & boys restroom by cafeteria, in the gym near storage room and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Repair exit sign near the lowest level stairwell of 8th grade going to the football field.  NFPA 101: 7.10.9.1
3. Stairwell and fire doors (upper level center and open stair area) shall not be propped open. NFPA 101: 7.2.1.8.2
2010/11:
1. Service emergency lights near 314, 307, 306 and throughout building.  NFPA 101: 7.9.3
2. Stairwell doors shall not be propped open by chairs.  NFPA 101: 7.2.1.8.1*
3. There shall be no combustibles stored in boiler room.  IFC 315.2.3
2011/12: NONE

CUMBERLAND ELEMENTARY
2009:
1. Service emergency lights at the entry to the cafeteria, by the upper level stairwell, in the stairwell by the library and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service exit sign in the library.  NFPA 101: 7.10.9.1
3. Relocate smoke detectors ( two in the yellow brick hall and by #145,254, and 257) located closer than 3 ft. of an air diffuser.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
4. There shall be no storage in stairwells (by #158 and next to Music).  NFPA 101: 7.2.2.5.3
5. Seal penetrations above the panel room door by #219.  NFPA 101: 8.3.4.1
2010/11:
1. Service emergency lights nearest lower level elevator by #145, in stairwell by #240, by #238, by #221, in yellow brick hall and throughout. NFPA 101: 7.9.3
2. There shall be no storage in stairwells (by #135 and by Music room). NFPA 101: 7.2.2.5.3*
3. Grills shall not be stored within ten feet of the building.  Remove immediately. IFC 308.3.1
4. Smoke detector shall be no closer than three feet to an air diffuser.  NFPA 72: 5.7.4.1
5 Service exit sign outside boiler room. NFPA 101: 7.10.9.1
2011/12:
1. Service emergency lights outside the office, by water fountain by elevator, by #135, in stairwell across from #240, by music room and throughout. NFPA 101: 7.9.3
2. There shall be no storage in stairwells (remove desks by #435, color paper rolls by 158, item by music).  NFPA 101: 7.2.2.5.3*
3. Remove excess storage in the sprinkler room for access to equipment.  IFC 315.2.3

DAN MILLS ELEMENTARY
2009:
1. Service emergency lights in stairwell across from library, in upper stairwell by elevator, in stairwell across from C15 and in corridor by C15.  Periodic testing is required.  NFPA 101: 7.9.3
2. Relocate smoke detectors (by upper level stairwell near the elevator and outside C-9 & C-11) so that they are not located where airflow prevents operation of the detectors.  Detectors should not be located in a direct airflow nor closer than 3 ft.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
3. There shall be no storage in stairwells (lost and found clothing & other items and the trees by C15).  Remove all trash cans.  NFPA 101: 7.2.2.5.3*
2010/11:
1. Smoke detector shall be located no closer than 3 ft to an air diffuser (outside gym).  NFPA 72: 5.7.4.1
2. Service emergency lights by the upper level stair near elevator and across from the restrooms by the elevator.  NFPA 101: 7.9.3
2011/12:
1. Artwork shall not exceed 50% of wall (kindergarten and Art corridor).  NFPA 15.7.4.3
2. Service exit signs by #C16, D6, C1, upper level elevator and throughout as needed.  NFPA 101: 7.10.9.1
3. Kiln room shall be 1-hour rated with a 45-minute labeled fire door and door closer.  NFPA 101: 15.3.2.1
4. Smoke detector shall be located no closer than 3 ft to an air diffuser (kiln room).  NFPA 72: 5.7.4.1
5. Service emergency lights by the upper level stair near elevator and across from the restrooms by the elevator.  NFPA 101: 7.9.3

DODSON ELEMENTARY
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service fire extinguishers outside the cafeteria door#54 and in the library.  NFPA 10: 6.3.1
3. Relocate smoke detectors (by electrical room# 130) so that they are not located in a direct airflow nor closer than 3 ft. where airflow prevents operation of the detectors.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11:
1 Service emergency lights across main lobby and across from guidance.  NFPA 101: 7.9.3
2011/12:
1. Fire alarm panel in trouble mode.  NFPA 72: 10.2.1.2
2. Service emergency light by computer, by room #119.  NFPA 101: 7.9.2.3*
3. There shall be one window for rescue (Portable #4) and (Fun Company-Rearrange bookshelf so that window is clear).  NFPA 101: 15.2.11.1.1

DONELSON MIDDLE
2009:
1. Service emergency lights throughout the library and cafeteria and throughout as needed.  Periodic testing is required. NFPA 101: 7.9.3
2. There shall be no storage in stairwells.  Remove all chairs.  NFPA 101: 7.2.2.5.3*
2010/11: NONE
2011/12: NONE

DUPONT ELEMENTARY
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service exit sign in the cafeteria.  NFPA 101: 7.10.9.1
3. Relocate smoke detector (front lobby) so that it is not located in a direct airflow nor closer than 3 ft.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11: NONE
2011/12: NONE

DUPONT HADLEY MIDDLE
2009:
1. Several emergency lights were not working. Service emergency lights throughout.  Periodic testing is required.  NFPA 101: 7.9.3
2. Several doors throughout were secured in the open position. Classroom and egress corridor doors shall not be propped open.   NFPA 101: 7.2.1.8.2
3. Seal penetrations in the Annex corridor and near the lower level elevator of the gym.  NFPA 101: 8.3.5.1*
4. Repair stairwell door closer (by the lower level elevator in the gym).  NFPA 101: 7.2.1.8.2
2010/11:
1. Service emergency lights throughout as needed.  There are several not working throughout the building including the Annex building.  Periodic testing is required.  NFPA 101: 7.9.3
2. Exits shall not be obstructed (by custodian office).  Remove wagons and mats immediately.  NFPA 101: 7.1.10.1*
3. Rearrange smoke detector so that it is not located closer than 3 ft. to an air diffuser (in the storage closet across from the 2nd level elevator).  NFPA 72: 5.7.4.1
4. Seal penetrations in the corridor of the Annex building.  NFPA 101: 8.3.5.1*
5. Classroom and egress corridor doors shall not be propped open. (non-sprinklered areas)  Also stairwell doors shall not be propped open (lower level of gym).  NFPA 101: 7.2.1.8.1*
2011/12:
1. Service emergency lights in Alumni room, in cafeteria by custodian closet, by rooms #29, 23, throughout the 5th/6th grade wing including stairwells and throughout the building as needed.  NFPA 101: 7.9.3
2. The door connecting from Art to the Alumni room shall be unlocked for use as a 2nd exit during normal operating hours.  NFPA 101: 7.2.1.5.1 
3. Grills shall not be stored in the building.  IFC 308.3.1.1
4. Propane shall not be stored in the electrical room (outside across from Vocational building).  NFPA 30
5. Replace missing ceiling tile in lower level of gym by dance class & by the elevator.  NFPA 101: 8.4.2

DUPONT TYLER MIDDLE
2009:
1. Service emergency lights by Rm#112, in the lower level Stair by#112, in the gym on the cafeteria side, in the corridor to the Strings class and throughout as needed.  Periodic testing is required. NFPA 101: 7.9.3
2. Classrooms shall have not less than one outside window that remains clear, unobstructed, and operable for emergency rescue at all times. (Rm#212 does not have a window.)  NFPA 101: 15.2.11.1
3. Seal penetrations in the boiler room.  NFPA 101: 8.3.5.6.1
4. Replace mesh filters in kitchen hood system.  NFPA 96: 6.1.3
5. Add a smoke detector at the location of the fire alarm panel.  In areas that are not continuously occupied, automatic smoke detection shall be provided.  NFPA 72: 4.4.5*
2010/11:
1. Classroom (& egress corridor) doors shall not be propped open.  Remove door stoppers.  NFPA 101: 7.2.1.8.1*
2011/12:
1. Service emergency light in kitchen, gym entrance, girls locker room, and small gym.  NFPA 101: 7.9.2.3*
2. There shall be one window for rescue (room #212).  NFPA 101: 15.2.11.1.1

EAKIN ELEMENTARY
2009:
1. Artwork on walls shall not exceed 50% (kindergarten).  NFPA 101: 15.7.4.3
2. Service emergency light by the girls bathroom near #216.  NFPA 101: 7.9.3
3. Relocate the smoke detector on 2nd grade level near the stariwell so that it is not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11:
1. Smoke detectors shall be located no closer than 3ft to an air diffuser (front lobby).  NFPA 72: 5.7.4.1
2. There shall be no storage within 18 in of sprinkler head (teacher storage next to #206).  NFPA 25
3. Candles shall not be burned (Ms. Green's class).  Use warmer or plug-in.  IFC 605.6
4. Service emergency light outside boy's restroom by #218, in gym (Fairfax exit side).  NFPA 101: 7.9.3
2011/12:
1. Fire alarm panel in trouble

EAST END PREP
2009: Not open yet
2010/11: NONE
2011/12
1. Service emergency lights across from #606, in hall next to #606 and by the exit near the East End Prep Admin office.  NFPA 101: 7.9.3

EAST MAGNET HIGH SCHOOL
2009:
1. Service emergency lights in all stairwells and throughout as needed.  There were several that were not working throughout the building.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service fire extinguisher by the building engineer office.  NFPA 10: 6.3.4
2010/11:
1. Service sprinkler system annually.  NFPA 25: 5.2.1.1
2. Service exit signs by #405, in the 4th floor auditorium, by 3rd floor elevator and Throughout as needed.  NFPA 101: 7.10.9.1
3. Service emergency lights in stairwell by #108, by #408, across from girls locker room and throughout as needed.  NFPA 101: 7.9.3
4. Seal penetrations in Chemistry storage next to #406.  NFPA 101: 8.4.4.1
5. There shall be no storage in stairwell (across from #108).  NFPA 101: 7.2.2.5.3*
6. Replace missing glass in auditorium door near #400.  NFPA 101: 8.3.3.6*
2011/12:
1. Service emergency lights in the stairwell from and in the small gym/stage, by #101 and 104, in the cafeteria, gym, and auditorium and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Relocate "mechanical lift" so that it does not block exit doors by concession area.  NFPA 101: 7.1.10.1*

EAST MAGNET MIDDLE
2009:
1. Service emergency light in the stairwell by room#407.  Periodic testing is required.  NFPA 101: 7.9.3
2010/11:
1. Service Class K fire extinguisher in the kitchen.  NFPA 10: 6.3.1
2. Service emergency light in stairwell by #209.  NFPA 101: 7.9.3
3. Seal penetrations over gym (B2) door across from #100.  NFPA 101: 8.4.4.1
4. Stairwell door shall not be propped open (by #106).  Repair magnetic hold open device or keep door closed.  NFPA 101: 7.2.1.8.1*
2011/12:
1. Sprinkler system shall be serviced annually.  NFPA 25: 5.2.1.1
2. Service emergency light in stairwell in stairwell near #202.  NFPA 101: 7.9.3

ENSWORTH HIGH
2009: N/A 4 violations
2010/11: N/A 1 violation
11/12: N/A 2 violaton

EWING PARK MIDDLE
2009: CLOSED
10/11: CLOSED
11/12: CLOSED

FALL HAMILTON ELEMENTARY
2009:
1. Service emergency lights in the gym, by the upper level elevator, in the kitchen, and by the stairwell nearest #321.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service exit signs in the stairwell to the front courtyard, in the front office and  in the lower level stair near Rains Ave.   NFPA 101: 7.10.9.1
3. Relocate the smoke detector in the custodian office so that it is not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11:
1. Service emergency light by elevator room.  NFPA 101: 7.9.3
2. Service exit signs near front lobby, across from #210 and in upper and lower stairwells.  NFPA 101: 7.2.12.3.5.2
2011/12:
1. Service emergency lights in the stairwell next to the gym, in corridor before room #314, 318, 212, by the Conference room and throughout.  Periodic testing is required.  NFPA 101: 7.9.3
2. Replace ceiling tile by#206, 210 and throughout various areas.  NFPA 101: 8.4.2
3. Remove excess storage from electrical panel room across from the office.  NFPA70: 110.26

GATEWAY ELEMENTARY
2009:
1. Service emergency light across from the front office.  Periodic testing is required. NFPA 101: 7.9.3
2. Seal penetrations above the bookroom, in B-12 and in most of the classrooms.  NFPA 101: 8.3.5.6.1
3. Service exit sign by the stage.  NFPA 101: 7.10.9.1
2010/11: Under renovations
2011/12:
1. Service emergency lights in the gym, in stairwell by locker 491 and throughout the building.  NFPA 101: 7.9.3
2. Classroom (& egress corridor) doors shall not be propped open. (#208).  NFPA 101: 7.2.1.8.1*
3. Resource room #200 in stairwell shall not be propped open.  NFPA 101: 7.2.1.8.1*
4. Provide a door closer for main office door.  NFPA 101: 7.2.1.8
5. Rearrange table so that 2nd exit (in Encore) is accessible.  NFPA 101: 7.1.10.1*
6. There shall be no storage in panel room across from small gym.  NFPA 70-110.26

GLENCLIFF ELEMENTARY
2009:
1. Service emergency lights by #113 and by #301.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service and tag the fire extinguisher nearest #106.  NFPA 10: 6.3.4
3. Kitchen hood filters shall be installed properly (vertically).  NFPA 96: 6.2.5
2010/11:
1. Kitchen hood filters shall be installed properly.  NFPA 96: 6.2.5
2. Gas fueled lawn equipment shall no be stored in the building.  IFC 313.1
2011/12:
1. Service emergency lights on both sides of the fire doors toward the gym and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Maintain 6 ft. corridor width (Pre-K).  NFPA 101: 15.2.3.2
3. There shall be 3 ft. clearance around mechanical and electrical equipment (back side of library).  NFPA 70: 110.26 (A)
4. Kitchen hood filters shall be installed properly.  NFPA 96: 6.2.5

GLENCLIFF HIGH
2009:
1. Service emergency light in the corridor outside of the boiler.  Periodic testing is required.  NFPA 101: 7.9.3
2. Provide exit signs in the following corridors:  near rooms #148 and 118-A, behind the big gym, and outside the training room.  NFPA 101: 7.7.3
3. Provide emergency lights for the serving line area.  NFPA 101: 7.9.1.1
4. There shall be no storage in the boiler room.  NFPA 1: 10.19.5.1
5. Fueled lawn equipment shall not be stored inside the building.  NFPA 1: 10.19.7
6. Grills (two of them) are prohibited from being stored inside the building.  NFPA 1: 10.11.7
7. Seal penetrations in the electrical room outside of the library.  NFPA 101: 8.3.5.1*
8. The exit doors from the stairwell near #130 shall not be chained. Unchain immediately.  NFPA 101: 7.1.10.1*
2010/11: NOT AVAILABLE
2011/12:
1. Service emergency lights in the library, auditorium, by the cafeteria, by room #5, and throughout. Periodic testing is required.  NFPA 101: 7.9.3
2. Service exit light in auditorium.  NFPA 101: 7.9.10.1*
3. There shall be a smoke detector in front of the elevator.  NFPA 72: 6.16.3.4
*Remember to replace ceiling tile after repairs.

GLENDALE ELEMENTARY
2009:
1. Service kitchen suppression system every six (6) months.  NFPA 96: 11.2.1
2. Artwork shall not exceed 50% of the wall.  NFPA 101: 15.7.4.3
3. Storage in the boiler room shall be separated by a 1 hour fire barrier and door or removed.  NFPA 101: 8.7.1.1*
2010/11: NONE
2011/12:
1. Lunchroom exterior exit shall not be blocked.  Rearrange before & after care tables, toys, and other equipment so that the exit is free of obstructions.  NFPA 101: 7.1.10.1*
2. Replace missing fire extinguisher in the electrical room across from the gym.  NFPA 10:1.5.3
3. There shall be 3 ft clearance around electrical panels and mechanical equipment (across from gym).  NFPA 70: 110.26
4. Sprinkler equipment shall not be blocked by toys and equipment (gym storage room).  NFPA 25: 5.2.2.2

GLENGARRY ELEMENTARY
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Classroom and egress corridor doors shall not be propped open (library and Rms#111, 125 & 131).  Repair door #110 so that it no longer "sticks" to the floor preventing closure.  NFPA 101: 7.2.1.8.1*
2010/11: NONE
2011/12:
1. Service emergency lights in the cafeteria, inside & outside the library, in boys restroom #1207 and throughout as needed.  Periodic testing is required.  Repair emergency light by #118.  NFPA 101: 7.9.3
2. Adjust the chain on the magnetic hold open device for the fire doors so that the closes on release (middle hall of library section).  NFPA 101: 7.2.1.8.1*
3. Replace ceiling tile throughout including gym & gym storage area. NFPA 101: 8.4.2
4. There shall be no storage within 18 inches of sprinkler heads.  NFPA 13: 8.5.6.1
5. Fire doors in the new 2nd grade wing shall not be propped open.  Compartmentation shall be maintained.  NFPA 101: 15.3.7.1
6. Replace missing sprinkler heads in spare supply box in the sprinkler room.  There shall be a minimum of six.  NFPA 25: 5.2.1.3

GLENN ENHANCED OPTION ELEMENTARY
2009:
1. Service exit sign by upper level elevator.  NFPA 101: 7.10.9.1
2. Service emergency light in the cafeteria on the alley side.  Periodic testing is required.  NFPA 101: 7.9.3
3. Relocate the smoke detector by Rooms#111 and 117 so that it is not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
4. Provide a smoke detector for elevator lobby area.  NFPA 72: 6.16.3.4
5. Stairwell doors (at the front entrance) shall not be propped open.  Repair magnetic hold open device or keep doors closed.  NFPA 101: 7.2.1.8.1
2010/11:
1. Service emergency lights in gym and in library.  NFPA 101: 7.9.3
2. There shall be a smoke detector in front of upper level elevator.  NFPA 72: 5.7.4.1
3. Seal penetration in upper level stair near elevator (behind emergency light).  NFPA 101: 8.4.4.1
2011/12:
1. Service emergency light across from #107, in Music room, next to 102, cafeteria and throughout.  NFPA 101: 7.9.3
2. There shall be no storage in the stairwell.  NFPA 101: 7.2.2.5.3

GLENVIEW ELEMENTARY
2009:
1. Relocate the smoke detector in the front entry foyer, by Room#20, and by Room#124 so that they are not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
2. There shall be no storage in the boiler room, electrical room (lower level) nor the elevator room.  NFPA 1: 10.19.5.1
3. Service emergency light by Room#112.  Periodic testing is required.  NFPA 101: 7.9.3
4. Seal penetrations in stairwell #2 (lower level), in the janitors' closet near Room#124, and above the door in the electrical panel room (lower level).  NFPA 101: 8.3.5.1
2010/11:
1. Fire alarm panel in trouble (Supervisory). Repair immediately.  NFPA 101: 4.6.12.1
2011/12:
1. Service emergency lights in stair #1 (upper and lower), by lower level exit by dev., by room # 12, 14, 16, 20 (entire lower level corridor) and throughout building.  NFPA 101: 7.9.3
2. Stairwell doors shall not be propped open (upper "sticking" and lower wedged and by room #26 (upper and lower).  NFPA 101: 7.2.1.8.1*
3. There shall be a wrench in sprinkler room spare box.  NFPA 13: 6.2.9.6

GOODLETTSVILLE ELEMENTARY
2009:
1. Service emergency lights above the Presidential photo display and by the exits near the P.E. office.  Periodic testing is required.  NFPA 101: 7.9.3
2. Exits shall be free and clear at all times.  NFPA 101: 7.1.10.1* 
3. Seal penetrations in the boiler room.  NFPA 101: 8.3.5.1*
2010/11: NONE
2011/12:
1. Service fire extinguisher in #7.  NFPA 10: 6.3.1
2. Classroom doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
3. Service emergency light by Room #1.  NFPA 101: 7.9.2.3*

GOODLETTSVILLE MIDDLE
2009:
1. Seal penetrations in the stairwell by #203  and above the library door.  NFPA 101: 8.3.4.1
2. Classrooms (two Vocational classrooms) shall have one outside window that remains clear, unobstructed, and operable for emergency rescue at all times.   NFPA 101: 15.2.11.1
3. Add a smoke detector to the room that houses the school alarm panel.  In areas that are not continuously occupied, automatic smoke detection shall be provided at the location of each fire alarm control unit to provide notification of fire at that location.  NFPA 72: 4.4.5*
4. There shall be no storage in stairwells. Remove chairs.  NFPA 101: 7.2.2.5.3.2
5. Classroom doors (ISS) shall be 20 minute fire-rated.  NFPA 101: 8.3.4.2
2010/11:
1. Classroom (& egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
2. Provide documentation that glass in office door & in corridor by #201 is fire rated.  NFPA 101: 15.3.6
3. Service emergency lights in gym & in stairwell near #201.  NFPA 101: 7.9.3
2011/12
1. Fire alarm panel in trouble.
2. Service emergency lights by rooms 5, 20, 48, gym (including locker rooms), and kitchen.

GOWER ELEMENTARY
2009:
1. Service emergency lights next to Room #102, by the restrooms near the cafeteria, and in the front foyer next to Speech.  Periodic testing is required.  NFPA 101: 7.9.3
2. There shall be a pull station located in a central area to activate the fire alarm system.  NFPA 101:  15.3.4.2.3.2*
2010/11:
1. Service emergency lights outside the office, by #102, by the bookstore, in the lower level boys restroom,  by the restrooms near teacher's lounge and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Repair ceiling tile in the elevator room.  NFPA 101: 8.4.2
3. Kitchen hood filters shall be installed properly.   NFPA 96: 6.2.5
2011/12:
1. Service emergency lights by Speech room, by lower level stairs, by room 203, in cafeteria and kitchen and throughout the building.  NFPA 101: 7.9.3
2. Stairwell door on lower level shall not be propped open.  NFPA 101: 7.2.1.8.1*
3. Kitchen hood filters shall be installed properly.  NFPA 96: 6.2.5

GRAMAR MIDDLE
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service emergency lights by Rm#221, #202, and in the stairwell by #202.  Periodic testing is required.  NFPA 101: 7.9.3
3. Repair fire door by #223 so that it closes on alarm (sticking on the floor).  NFPA 101: 7.2.1.8.2
4. Service fire extinguisher in Rm#124.  NFPA 10: 6.3.1
2010/11:
1. Service emergency light by Rm #207.  Periodic testing is required.  NFPA 101: 7.9.3
2. Exits shall be free and clear. Rearrange soccer goals so they do not block gym exit outside.  NFPA 101: 7.1.10.1*
2011/12:
1. Service emergency lights in the main office, cafeteria, kitchen, across from #111, and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Repair door closer on the stairwell by #202 and adjust door so that it closes completely.  NFPA 101: 7.2.1.8.1*
3. Repair hole in ceiling in storage room across from #200.  NFPA 101: 8.4.2
4. Replace missing sprinkler heads in spare supply box in the sprinkler room.  There shall be a minimum of six.  NFPA 25: 5.2.1.3

GRANBERRY ELEMENTARY
2009:
1. Service emergency lights by #123 and #130.  Periodic testing is required.  NFPA 101: 7.9.3
2. Classroom and egress corridor doors shall not be propped (non-sprinklered wing).  NFPA 101: 7.2.1.8.2
3. Classrooms (non-sprinklered wing) shall have one window free and clear for emergency rescue at all times.  NFPA 101: 15.2.11.1
4. Seal penetrations above the boiler room door.  NFPA 101: 8.5.6.3
2010/11:
1. There shall be no storage in mechanical (by 102, 106, and throughout). NFPA 1-10.19.5.1
2. Portables shall have one window for rescue (ELL and Music). NFPA 101: 15.2.11.1.1
3. Repair door closers on room #133.  NFPA 101: 7.2.1
4.  Provide door closers for room #134 (Art) and Consulting teacher room by #120. NFPA 101: 7.2.1.8
5. Classroom doors shall not be propped open (non-sprinklered areas). NFPA 101: 7.2.1.8.1*
6. Electrical panels shall have three (3) feet clearance (Throughout). NFPA 70: 110.26
2011/12:
1. Classroom shall have one window for rescue (Art Portable and Portable 492).  NFPA 101: 15.2.11.1.1
2. Classroom doors shall not be propped open.  Non sprinklered portion (#124, 122, 119, 116 and throughout)  NFPA 101: 7.2.1.8.1*

HG HILL MIDDLE
2009:
1. Service emergency lights in the gym by the boys locker room, outside of the gym, and at the rear of stage.  Periodic testing is required. NFPA 101: 7.9.3
2010/11: NONE
2011/12:
1. Service emergency lights by room #100, music, restrooms, library, throughout the gym and throughout building as needed.  NFPA 101: 7.9.2.3*

HARPETH VALLEY
2009:
1. Fire drills shall be conducted monthly and documented.  NFPA 101: 15.7.2.2
2. Service emergency lights in the library, by #229, by the bookstore, across from the custodian closet near the bookstore and outside media center.  Periodic testing is required.  NFPA 101: 7.9.3
3. Artwork shall not exceed 50% of wall space (especially hall near #141).  NFPA 101: 7.9.1.1
2010/11:
1. Service emergency lights by the cafeteria serving line, by #235, #194, and #150, at the exit to the kindergarten playground and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service Class K fire extinguisher in the kitchen.  NFPA 10: 6.3.1
3. There shall be no storage in the electrical panel room (next to the boiler room).  NFPA 70: 110.26
2011/12
1. Fire alarm panel was in other than normal mode.  Repair immediately.  NFPA 72: 10.2.1.2
2. Service emergency lights near the Community Room, by the computer repair room and in the library and cafeteria.  NFPA 101: 7.9.3
3. Replace spare sprinkler heads in the storage box in the sprinkler room.  NFPA 13: 6.2.9.1

HARRIS HILLMAN SPECIAL ED SCHOOL
2009:
1. Service emergency lights in E POD hall.  Periodic testing is required. NFPA 101: 7.9.3
2. Artwork shall not exceed 20%.  NFPA 101: 7.9.3
2010/11:
1. Kiln shall be stored properly in a fire-rated room.  NFPA 101: 8.3.5.1*
2. Seal penetrations in boiler room.  NFPA 101: 8.4.4.1
2011/12:
1. Fire extinguishers throughout shall be serviced annually.  NFPA 10: 6.3.1

HATTIE COTTON ELEMENTARY
2009:
1. Service exit sign near Room #203.   NFPA 101: 7.10.9.1
2. Remove gym equipment so that the exit from the gym is unobstruced.  NFPA 101: 7.1.10.1
2010/11: NONE
2011/12:
1. Sprinkler room shall have six (6) spare heads.  NFPA 13: 6.2.9.1
2. There shall be a wrench in sprinkler room.  NFPA 13: 6.2.9.6

HAYNES MIDDLE
2009: NONE
2010/11: NONE
2011/12:
1. Smoke detector shall be located no closer than 3 ft to an air diffuser. (front foyer)  NFPA 72: 5.7.4.1

HAYWOOD ELEMENTARY
2009:
1. Classrooms (P-2, P-3, and 20) shall have not less than one outside window that remains clear, unobstructed, and operable for emergency rescue at all times. Also, Rm#5 was padlocked.  NFPA 101: 15.2.11.1
2. Classroom doors #5, 7, 9, cafeteria and throughout shall not be propped open.  NFPA 101  7.2.1.8.1
3. Exits and exit corridors shall remain free and clear of obstructions.  Remove the table and other items from hall across from #14-A.  NFPA 101: 7.1.10.1
2010/11:
1. Service exit signs throughout the cafeteria, by #19, and at the ramp towards gym area.  NFPA 101: 7.10.9.1
2. Seal penetrations in the AV room.  NFPA 101: 8.3.5.1*
3. Classrooms (P4) shall have one outside window that remains clear, unobstructed, and operable for emergency rescue at all times. Also, rooms#11, 13, 14, 15, 16, 18 shall not be padlocked.  NFPA 101: 15.2.11.1.1
4. Classroom (and egress corridor) doors shall not be propped open.  Remove door stoppers throughout.  NFPA 101  7.2.1.8.1*
5. Provide a slip resistant walking surface for exiting by room#114.  NFPA 101: 7.1.6.4*
6. Service fire extinguisher in the Music portable (P1).  NFPA 10: 6.3.1
7. There shall be a pull station located in a central area (main office) to activate the fire alarm system.  NFPA 101:  15.3.4.2.3.1*
2011/12:
1. Fire alarm panel in trouble mode. Repair immediately.  NFPA 72: 10.2.1.2
2. Classrooms (P7) shall have one outside window that remains clear, unobstructed and operable for emergency rescue at all times. Also, rooms#5, 9, 13, 19 or any others shall not be padlocked.  Unlock them daily.  NFPA 101: 15.2.11.1.1
3. Maintain 6 ft. corridor width (by exit near room#4).  NFPA 101: 15.2.3.2

HEAD MIDDLE
2009:
1. Service emergency lights in the gym foyer (cafeteria side), in the cafeteria (gym side), near #227 and in the boiler room.  Periodic testing is required.  NFPA 101: 7.9.3
2010/11:
1 Service emergency lights by #106, by exit from main building to gym, in gym, by #127.  NFPA 101: 7.9.3
2. Fire alarm panel in trouble.  Repair immediately.  NFPA 101: 4.6.12.1
2011/12:
1. There shall be a spare sprinkler head box in the sprinkler room with a minimum of 6 spare heads and a spare wrench.  NFPA 101: 13.6.2.9
2. Service emergency lights by #234, near library main entrance, by 1st floor elevator and by 129.  NFPA 101: 7.9.3

HENRY MAXWELL
2009:
1. Service emergency lights in the front lobby, outside the restrooms across from the dining hall, in the receiving hall, in the gym entry, by #111, 203, and 219, by the restrooms near the elevator, by the stair near the library and throughout as needed.  Periodic testing is required. NFPA 101: 7.9.3
2010/11
1. Service emergency lights in gym and outside gym, by restrooms outside cafeteria, by #106, #203, in stairwell nearest #203 & throughout.  NFPA 101: 7.9.3
11/12:
1. Service emergency lights in gym (1), in stairwell across from elevator, girls restroom (upstairs), nest to #219, throughout library and stairwell across from #112.  NFPA 101: 7.9.3
2. Sprinkler room shall have 6 spare sprinkler heads in box.  NFPA 13: 6.2.9

HERMITAGE ELEMENTARY
2009:
1. Service emergency lights in the cafeteria.  Periodic testing is required. NFPA 101: 7.9.3
2. Classroom and egress corridor doors (Rm#108, the cafeteria and the front office) shall not be propped open.  NFPA 101: 7.2.1.8.2
2010/11: NONE
11/12: NONE

HICKMAN ELEMENTARY
2009: NONE
2010/11: NONE
2011/12:
1. Replace missing ceiling tile in lobby.  The therapeutic swing shall not cause problems for sprinkler initiation.  NFPA 101: 8.4.2

HILLSBORO HIGH
2009:
1. Fire alarm panel in trouble.  Repair immediately.  NFPA 101: 4.6.12.1
2. Service emergency lights by#120 and #146, in the gym and in the gym foyer.  Periodic testing is required. NFPA 101: 7.9.3
3. There shall be no storage in stairwells (including drink machines, carts and ladders).  NFPA 101: 7.2.2.5.3*
4. Kitchen hood filters shall be installed properly.  They are turned the wrong way.  NFPA 96: 6.2.5
5. Add smoke detector in front of elevator.  NFPA 72: 6.16.3.5
6. Automatic-closing fire doors shall have smoke detectors for release of magnetic hold-open devices.  NFPA 80: 2-1.4.2
7. Repair locker room door panic hardware.  NFPA 101: 7.2.1.7.1
8. Provide emergency lights across from mechanical and outside upper level gym.  NFPA 101: 7.9.1
2010/11:
1. Fire alarm panel showing trouble.  Repair immediately.  NFPA 101: 4.6.12.1
2. Kitchen filters (in hood) shall be installed properly.  NFPA 96: 6.2.5
3. Service emergency lights in auditorium (front left by storage and rear right), across from elevator and library.  NFPA 101: 7.9.3
4. There shall be a smoke detector within 5ft of elevator.  NFPA 72: 6.16.3.4
5. There shall be a smoke detector located at magnetic hold devices on fire doors throughout.  NFPA 80: 2-1.4.2 There shall be no storage in stairwells (across from auditorium).  NFPA 101: 7.2.2.5.3*
2011/12:
1. Service emergency lights throughout.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service fire extinguishers throughout including Class K in the kitchen.  NFPA 10: 6.3.1
3. Service exit lights in the large gym.  NFPA 101: 7.10.9.1
4. There shall be a smoke detector in front of the elevator (by #209).  NFPA 72: 6.16.3.4
5. Seal penetrations throughout the corridor by #117 to limit the spread of smoke and fire.  NFPA 101: 8.3.4.1
6. Kitchen hood filters shall be installed properly.  NFPA 96: 6.2.5

HILLWOOD HIGH
2009:
1. Service emergency lights by the 10th grade office, by #094, in the stairwell to Arts hall across from main office, throughout the gym building and throughout as needed.  Periodic testing is required. NFPA 101: 7.9.3
2. Service exit signs in the library and throughout the gym building.  NFPA 101: 7.10.9.1
3. Add exit signs throughout the lower level of the main building near Arts.  NFPA 101: 7.10.1.2*
4. Seal penetrations in the custodian closets by the concessions stand, across from the stairwell near the courtyard and in the boiler room.  NFPA 101: 8.3.5.1*
5. Stairwell doors shall not be propped.  NFPA 101: 7.2.2.5.3.2*
6. There shall be a smoke detector by the elevator near #151.  NFPA 72: 6.16.3.5
7. Kitchen hood filters shall be installed properly.  They are turned the wrong way.  NFPA 96: 6.2.5
8. Repair stairwell door closer across from #054.  NFPA 101: 7.2.1.8.1*
9. Classroom exit doors shall not be blocked #092 (chord hazard).  NFPA 101: 7.1.10.1*
2010/11:
1 Fire alarm panel in trouble.  Repair immediately.  NFPA 101: 4.6.12.1
2. Kitchen suppression system shall be services every 6 months.  Kitchen separate from cafeteria.  NFPA 96: 11.2.1
3. Seal penetrations in mechanical closet next to elevator/outside cafeteria, janitor's closet across from concession stand.  NFPA 101: 8.4.4.1
4. Service emergency lights in small gym and women's locker room and outside small gym (track side).  NFPA 101: 7.9.3
5 Repair "vent" openings in corridor/large girls locker room #113.  NFPA 101: 8.3.5.1
2011/12:
1. Service emergency lights in the cafeteria and kitchen, in the larger gym locker room, in stairwell by #127 and throughout. Periodic testing is required.  NFPA 101: 7.9.3
2. Service fire extinguisher by #O92.  NFPA 10: 6.3.1
3. Replace missing  ceiling tile in various areas on the lower level of C bldg., in the custodian closet by #52 and throughout as needed.  NFPA 101: 8.4.2
4. Replace panel covers in custodian closet by #52.  NFPA 70: 314.25
5. Provide flammable liquids cabinet for Scinece room #240.  NFPA 30.

HULL-JACKSON SCHOOL
2009: NONE
2010/11:
1 Dryer shall be vented to the outside.  NFPA 211: 10.7.3.3
2 There shall be no storage in stairwells.  NFPA 101: 7.2.2.5.3*
11/12: NONE

HUME-FOGG MAGNET HIGH
2009:
1. Repair the opening in the stairwell from the gym (shared wall with coach's office).  NFPA, , 101: 8.2., 3.2.4,, 20, 1, 0/11 : NONE
2011/12:
1. Service exit, signs near 416., &, nbsp; NFPA 101: 7.10.9.1<, br />2. Seal penetrations above room# 416, 404, 402, 403, 405 and spaces in transoms in various locations throughout (including library, 303, outside Guidance).  NFPA 1, 01: 8.3.4.1
3. Seal penetrations in stairwell lobby near library, near 305, near 213 and throughout.  NFPA 101: 8.3.5.1
4. Service emergency lights in kitchen.  NFPA 101: 7.9.2.3*

HUNTERS LANE HIGH
2009:
1. Fire drills shall  be conducted monthly (+ one additional one within the first 30 days) and documented.  NFPA 101: 15.7.2.2
2. Service emergency lights at the beginning of the Vocational hall and by the panel room in the Vocational hall.  Periodic testing is required. NFPA 101: 7.9.3
3. Service fire extinguisher in the kitchen by the dock.  NFPA 10: 6.3.1
4. Provide a smoke detector in the elevator lobby.  NFPA 72: 6.15.3.5
5. Replace ceiling tile behind the stage.  NFPA 101: 8.3.4.1
6. Kitchen grease filters shall be installed at an angle not less than 45 degrees from the horizontal.  NFPA 96: 6.2.3.5
2010/11:
1 Service emergency light at the 210-221 hall entry, ramp on 200 side.  NFPA 101: 7.9.3
2 Electrical panel shall have 3 ft working room.  NFPA 70: 110.26
3 Smoke detector shall be no closer than 3 ft to an air diffuser. (By Assistant Principal's side door/121-133 hall).  NFPA 75: 5.7.4.1
2011/12:
1 Service emergency lights throughout. Periodic testing is required.  NFPA 101: 7.9.3
2 Service fire extinguishers throughout.  NFPA 10: 6.3.1
3 Replace ceiling tile in band room and in various area throughout.  NFPA 101: 8.4.2
4 There shall be a smoke detector in front of the elevator (lower level).  NFPA 72: 6.16.3.4
5 The sprinkler room shall have a spare box with six (6) spare heads and a wrench.  NFPA 13: 5.2.1.3 and 6.2.9.6

ISAIAH T CRESWELL MIDDLE
2009:
1. Service emergency lights in the blue stairwell (upper and lower level).  Periodic testing is required.   NFPA 101: 7.9.3
2. Exits and exit corridors shall remain free and clear of obstructions.  Remove the band instruments outside of the Band room.  NFPA 101: 7.1.10.1
3. There shall be no exposed wires (wrapped around emergency lights in Band room).  NFPA 70: 110-27
2010/11: NONE
2011/12:
1. Repair large opening in ceiling in Women's restroom by elevator on main level.  NFPA 101: 8.3.4.1
2. Repair exit sign on boys locker room side of gym.  NFPA 101: 7.10.9.1
3. Service emergency light by #104.  NFPA 101: 7.9.3

INGLEWOOD ELEMENTARY
2009: NONE
2010/11:
1. Service emergency lights by the 2nd floor bookroom, at the ramp by #216, in the kitchen, across from the stairwell by #211 and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2011/12:
1. Service emergency lights near room 115, in the stairwell by room 109 (upper and lower), across from 215, restrooms by room 224, by rooms 229, 132, and 128 and throughout the school.  NFPA 101: 7.9.3
2. Replace (cut) ceiling tile in various areas.  NFPA 101: 8.4.2
3. Extension cords shall not be used in place of permanent wiring (room 224).  IFC 605.5

JE MOSS ELEMENTARY
2009:
1. Seal penetrations in the boiler room.  NFPA 101: 8.3.5.1*
2. Service the emergency light in the front office. Periodic testing is required.  NFPA 101: 7.9.3
3. Fueled lawn euiqpment shall not be stored in the building (unless feul is emptied).  NFPA 1: 10.19.7
4. Artwork and teaching materials shall not exceed 50% of the wall area.  NFPA 101: 15.7.4.3
2010/11:
Repeated Violation:
1.  Relocate smoke detectors by #127 and 129 so that they are located no closer than 3 feet from air diffuser.  NFPA 72: 5.7.4.1
2011/12:
1. Service emergency lights at the corner to the gym and in the gym (far side).  Periodic testing is required.  NFPA 101: 7.9.3
2. Re-evaluate and provide emergency lighting between room#112 and the main foyer and throughout as needed.   NFPA 101: 7.9.2.3*

JOHN F KENNEDY MIDDLE
2009:
1. Relocate the smoke detectors so they are not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft. (by #1070, by upper level elevator and by the Mission and Vision sign).  NFPA 72: 5.7.4.1 (A-5.7.4.1)
2. Replace missing fire extinguisher by the upper level elevator.  NFPA 10: 1.5.2
3. Remove excess storage from mechanical room #2125.  NFPA 1: 10.19.5.1
4. Stairwell door (#2074) shall not be propped open.  Repair hold open device.  NFPA 101: 7.2.1.8.1.*
2010/11:
1.  Service emergency lights in the kitchen, gym and THROUGHOUT.  Periodic testing is required.  NFPA 101: 7.9.3
2. Relocate smoke detector (by 2nd level elevator) so that it is not closer than 3 ft. to an air diffuser.  NFPA 72: 5.7.4.1
3. There shall be no storage in stairwells.  Remove bench and plant.  NFPA 101: 7.2.2.5.3*
2011/12:
1. Fire alarm panel in trouble mode.  Repair immediately.  NFPA 101: 4.6.12.1

JT MOORE
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Classroom (and egress corridor) doors shall not be propped open (rooms#2, 6, 21, 22, 32, both Special Ed. classes and the main office).  NFPA 101: 7.2.1.8.1*
3. Service emergency lights across from the main office, library and Assistant Principal's office, in the little gym, library and cafeteria and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2010/11:
1. Service emergency lights by #B24, B13 and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2011/12:
1. Fire alarm panel in trouble.  Repair immediately.  NFPA 72: 6.8.1.1
2. Fire drills shall be conducted and documented monthly.  NFPA 101: 15.7.2.2
3. Service emergency lights in the Strings room, computer lab by Strings room, main corridor near C1 and throughout as needed.  NFPA 101: 7.9.3
4. Service exit sign by #B22.  NFPA 101: 7.10.9.1
5. There shall be one window free and clear for rescue.  NFPA 101: 15.2.11.1.1
6. Extension cords shall not be used in place of permanent wiring including rooms#B14, B11, and B21.  IFC 605.5

JERE BAXTER ALTERNATIVE LEARNING
2009:
1. Service emergency lights in cafeteria, by Stair E, in stairwell by #207 and gym.  Periodic testing is required.  NFPA 101: 7.9.3
2. Classroom doors on the 2nd level (including #212 &213) shall have self-closing or automatic-closing devices.  NFPA 101: 7.2.1.8.1
3. Repair exit sign in the gym.  NFPA 101: 7.10.9.1

4. There shall be one window free and clear for rescue.  NFPA 101: 15.2.11.1.1
2010/11:
1. Service emergency lights by #102, by exit near #101, by #205, by #212.  NFPA 101: 7.9.3
2. Classrooms shall have one window for rescue (#208 would not open).  NFPA 101: 15.2.11.1.1
3. Replace exit signs throughout gym.  NFPA 101: 7.10.1.2*
2011/12:
1. Service emergency lights throughout the building.  NFPA 101: 7.9.3
2. Classroom (& egress corridor) doors shall not be propped open including the cafeteria and throughout.  NFPA 101: 7.2.1.8.1*
3. Classrooms shall have one window for rescue (#208, 210, & 202).   NFPA 101: 15.2.11.1.1
4. Repair exit sign by #209 and 210.  NFPA 101: 7.10.9.1
5. Fire extinguisher shall be serviced and tagged.  NFPA 10: 6.3.1

JERE BAXTER MIDDLE
2009:
1. Service emergency lights by Rooms #101, 103, & 207, in  the library by the computers and in the cafeteris.  Periodic testing is required.   NFPA 101: 7.9.3
2. Relocate smoke detector (by Room#219 and two in the cafeteria) so that it is not located in a direct airflow nor closer than 3 ft. where airflow prevents operation of the detector.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
3. Service exit sign By Room #214.  NFPA 101: 7.10.9.1
4. There shall be no storage in panel and mechanical rooms (by #202 and in the library)/  NFPA 1: 10.19.5.1
2010/11: NONE
2011/12:
1. Service exit signs in the stairwell hall nearest #111 and next to room #119.  NFPA 101: 7.10.9.1
2. Service emergency lights in the stairwells by #111, 211 and by library, nearest rooms #116, 117, and 118, in all boys & girls restrooms and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
3. Repair stairwell door by #211 and outside of the library.  NFPA 101: 7.2.1.8.1*

JOELTON ELEMENTARY
2009:
1. Service emergency light by Room#137.  Period testing is required.   NFPA 101: 7.9.3
2. Service exit signs in the gym and kitchen.  NFPA 101: 7.10.9.1
3. Relocate smoke detector by Room#128 so that it is not located within 3 ft. (or less) of an air source.  NFPA 72: 5.7.4.1
2010/11: NONE
2011/12:
1. Service emergency lights in the kitchen and by room# 126.  Periodic testing is required.  NFPA 101: 7.9.3

JOELTON MIDDLE
2009:
1. Service emergency light by Room#137.  Period testing is required.   NFPA 101: 7.9.3
2. Service exit signs in the gym and kitchen.  NFPA 101: 7.10.9.1
3. Replace missing ceiling tile in the Art room and the elevator  room to limit the spread of fire and restrict the movement of smoke.  NFPA 101: 8.3.4.1
4. Combustible material shall not be stored in the elevator room nor the mechanical room across from Room #1.  NFPA 1: 10.19.5.1
5. Replace mesh filters in kitchen hood system.  NFPA 96: 6.1.3
2010/11:
1. Fire alarm in trouble mode. Repair immediately.  NFPA 101: 4.6.12.1
2. Service emergency lights near the lower level elevator, in the gym, in the boys locker room and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
3. Classroom (and egress corridor) doors shall not be propped open including the Principal's office and room #37.  NFPA 101: 7.2.1.8.1*
4. Seal penetrations in the mechanical room across from room #1 and in the boiler room.  NFPA 101: 8.3.5.1*
5. Repair opening in the wall next to stair outside cafeteria to maintain fire wall and separation.  NFPA 101: 8.3.5.1*
2011/12:
1. Service emergency lights in the stairwell across from room#28 and stairwell by library, by rooms#33, 2 and in the gym near the boy's locker room.  Periodic testing is required.  NFPA 101: 7.9.3
2. There shall be one window free and clear fro rescue (rooms#4 and 9).  NFPA 101: 15.2.11.1.1
3. Classroom (and egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.1*

JOHN EARLY MIDDLE
2009:
1. Seal penetrations in gym by exit nearest girls locker room and above ceiling @ the entry to girls locker room.  NFPA 101: 8.3.5.1
2. Replace ceiling tile @ entry to girls locker room to limit the spread of smoke and fire.  NFPA 101: 8.3.4.1
2010/11:
1.  Fire alarm panel in trouble.  Repair immediately.  NFPA 101:  4.6.12.1
2011/12:
1. Service emergency lights by #239.  NFPA 101: 7.9.3
2. There shall be an wrench in the spare sprinkler box in the sprinkler room.  NFPA 13:6.2.9.6

JOHNSON SCHOOL
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service emergency lights throughout.  Periodic testing is required. NFPA 101: 7.9.3
3. Service exit signs in the cafeteria and gym/auditorium.  NFPA 101: 7.10.9.1*
4. Seal penetrations in the boiler room, in 1st and 3rd floor storage closets, and by both 1st floor stairwells.  NFPA 101: 8.3.5.1*
5. Classroom and egress corridor (#205, 310, and Guidance office) doors shall not be propped open. Stairwell doors shall remain closed at all times as well.  Repair door closers (by #311).  NFPA 101: 7.2.1.8.2
2010/11:
1. Service emergency lights by #308, 210, 204, in the gym, caferteria, kitchen, stairwell to 1st floor,  and throughout.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service exit signs in the gym, by #209 and throughout.  NFPA 101: 7.10.9.1
3. Classroom (and egress corridor) doors shall not be propped open (main office and #306)  NFPA 101: 7.2.1.8.1*
4. Gym exit (2nd Av side) shall not be chained locked.  Also, this exit shall not be blocked by desks, chairs, etc.  Remove immediately.  NFPA 101: 7.1.10.1*
5. Cooking equipment (ovens in Culinary Arts) that produces grease-laden vapors shall be protected by fire-extinguishing equipment.  NFPA 96: 10.1.2
2011/12:
1. Stairwell doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
2. Replace missing fire extinguisher by #309.  NFPA 10: 1.5.7
3. Service emergency lights in stairwell across from #209, across from the main office, and by #204.  NFPA 101: 7.9.3
4. Service exit signs throughout including cafeteria and gym.  NFPA 101: 7.10.9.1

JONES PAIDEIA MAGNET ELEMENTARY
2009:
1. Service exit sign in the cafeteria.  NFPA 101: 7.10.9.1
2. Stairwell doors shall not be propped open (by the boiler room).  NFPA 101: 7.2.1.8.1*
2010/11:
1. Service emergency lights across from #201, next to the bathroom by #203 and next to #203.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service exit signs throughout.  Some were beeping.  NFPA 101: 7.10.9.1
3. There shall be no storage in stairwells. Remove desks and other items.  NFPA 101: 7.2.2.5.3*
2011/12: NONE

JULIA GREEN ELEMENTARY
2009:
1. Classroom and egress corridor doors shall not be propped open.  NFPA 101: 7.2.1.8.1
2010/11:
1. Service emergency light in basement classroom.  NFPA 101: 7.9.3
2. Service exit sign in basement classroom.  NFPA 101: 9.10.9.1
3. There shall be a smoke detector located at magnetic hold devices on fire doors throughout.  NFPA 80: 2-1.4.2
4. There shall be no storage in stairwells (to Encore class).  NFPA 101: 7.2.2.5.3*
2011/12:
1. Service emergency lights by room #10 & 12.  NFPA 101: 7.9.3

KIPP SCHOOL
2009:
1. Emergency egress and relocation drills shall be conducted monthly and be documented.  NFPA 101: 15.7.2.1
2. Seal penetrations in the corridor across from the office and in the janitors closet across from Room #301.  NFPA 101: 8.3.5.1
3. Replace ceiling tile missing outside the cafeteria and thorughout the building.    NFPA 101: 8.3.4.1
4. Egress corridor doors (classrooms) shall not be propped open.   Stairwell doors shall not be propped open either.  Repair door closers in stairwells near auditorim and on the 3rd floor across from  the elevator and also Rooms #300 and #301.   NFPA 101: 7.2.1.8.1
5. Service emergency lights throughout the stairwell by auditorium, by Rooms #102 and #200, and in the cafeteria.  Periodic testing is required.  NFPA 101: 7.9.3
6. Service exit signs in and near the auditorium, in the cafeteria, in the stairwell near the auditorium, by the 2nd level elevator and throughout as needed.  NFPA 101: 7.10.9.1
7. There shall be no storage in stairwells.  Remove ladder, trashcan and other combustible items.  NFPA 101: 7.2.2.5.3
8. Replace the door hardware (door knob) on Room #303.  NFPA 101: 8.2.2.5
9. Replace mesh filters.  Non-mesh filters shall be installed according to the manufacturer.   NFPA 96: 6.1.3
2010/11
1. Service (or repair) exit signs in both gyms and throughout as needed.  NFPA 101: 7.10.9.1
2. Service emergency lights outside main gym, by #300, in stairwell A and throughout as needed.  NFPA 101: 7.9.3
3. Seal penetrations by the wall of flags and above #204.  NFPA 101: 8.3.5.1*
2011/12:
1. Service emergency light in the gym.  Periodic testing is required.  NFPA 101: 7.9.3

KIRKPATRICK ELEMENTARY
2009:
1. Emergency egress and relocation drills shall be conducted monthly and be documented.  NFPA 101: 15.7.2.1
2. Service emergency lights inside the cafeteria, by #108 & 110, in the stairwell across from #107, across from the auditorium, in the 200 hallway and throughout.  Periodic testing is required.  NFPA 101: 7.9.3
3. There shall be 3 ft. clearance for electrical panels.  NFPA 70: 110-26(b)
4. Service exit sign in corridor just past data room.  NFPA 101: 7.10.9.1
5. Relocate the smoke detector by #107 so that it is not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
Note:  Remember to replace ceiling tile after ongoing work is complete.
2010/11
1. Fire alarm panel not in normal working condition. (Power off)  NFPA 101: 4.6.12.1
2011/12:
1. Service emergency lights in girls restroom across from library, in library, across from play room, in stairs by #214.  NFPA 101: 7.9.3
2. Fire door between gym and other part of building shall not be propped open.  Keep door closed for separation or repair magnetic hold device.  NFPA 101: 7.2.1.8.1*

LAKEVIEW ELEMENTARY
2009:
1. Service emergency lights in the cafeteria near the Music room entry and in the kitchen.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service fire extinguisher in the kitchen (Class K).  NFPA 10: 6.3.1
3. Relocate the smoke detector by the fire panel so that it is not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11:
1. Service emergency lights by Rooms# 8 and 28 and near the main lobby doors by the green area.  Periodic testing is required.  NFPA 101: 7.9.3
2. Kitchen hood filters shall be installed properly.  NFPA 96-6.2.5
2011/12:
1. Sprinkler system shall be serviced annually.  NFPA 25: 5.2.1.1
2. Service emergency lights in the cafeteria, gym and throughout as needed.  Periodic testing is required.    NFPA 101: 7.9.3
3. There shall be one window free and clear for rescue (Portable#10).  NFPA 101: 15.2.11.1.1
4. There shall be no storage within 3ft of mechanical or electrical equipment (blue pod and across from storage #32 in purple pod).  IFC 315.2.3
5. Junction boxes shall be covered (mechanical room-blue pod and across from #32-purple pod).  IFC 605.6
6. The use of extension cords shall not replace permanent wiring (library and throughout).  IFC 605.5
7. Sprinkler rooms shall be identified for the use of the fire department.  IFC 510.1
8. Replace missing sprinkler heads in spare supply box in the sprinkler room.  There shall be a minimum of six.  NFPA 25: 5.2.1.3

LEAD ACADEMY (UPPER)
2009:
1.  Stairwell door (upper level near office) shall not be propped open.  NFPA 101: 7.2.1.8.1
2010/11:
1. Fire alarm panel in other than normal mode.  Repair immediately.  4.6.12.1
2. Service emergency lights by room #5 and in the upper level "end" stair.  NFPA 101: 7.9.3
3. There is no usable space within stairwells.  Remove artwork, etc.  NFPA 101: 7.2.2.5.3*
4. Stairwell doors shall not be propped open.  NFPA 101:  7.2.1.8.1*
2011/12:
1. Service emergency lights by room #5, in upper and lower restrooms, in the middle stairwell, and throughout as needed.  Periodic testing is required.   NFPA 101: 7.9.3

LITTON MIDDLE
2009:
1. Service emergency lights in the stairwell near #215 and in the stairwell near the cafeteria. Periodic testing is required.  NFPA 101: 7.9.3
2. Service fire extinguisher outside the lower level center stairwell .  NFPA 10: 6.3.4
3. Exit doors shall not be blocked by equipment at the rear locker side of the gym.  NFPA 101: 7.1.10.1*
4. There shall be no storage in stairwells.  NFPA 101: 7.2.2.5.3.2
5. Seal penetrations inside and outside upper level center stairwell and above the the gym door.  NFPA 101: 8.3.5.1*
2010/11:
1. The fire alarm system was in trouble mode.  Repair immediately.  NFPA 101: 4.6.12.1
2. Stairwell doors shall not be propped open (near the elevator on the 1st and 2nd floors and acrosss from #801).  Remove any door stoppers and wedges.  NFPA 101: 7.2.1.8.1*
2011/12:
1. Service emergency lights across from #601, 100, 502, in & by the exit near #505, by the 2nd floor elevator, by #800 & throughout as needed.   Periodic testing is required.  NFPA 101: 7.9.3
2. Repair stairwell door so that it closes (by #802).  NFPA 101: 7.2.1.8.1*

LOCKELAND ELEMENTARY
2009: NONE
2010/11:
1. Fire alarm panel in trouble.  Repair immediately.  NFPA 101: 4.6.12.1
2011/12:
1. Service emergency lights by room #102 and in stairwell by room #102, 203 and entire corridor, gym, and cafeteria.  NFPA 101: 7.9.2.3*
2. There shall be no storage in stairwell including artwork.  NFPA 101: 7.2.2.5.3*
3. Rearrange kitchen equipment so that "pull ring" for suppression system is not blocked. NFPA 96: 10.5.1
4. Rearrange P.E. equipment so that exit is free and clear.  NFPA 101: 7.1.10.1*

MADISON MIDDLE SCHOOL
2009:
1. Service emergency lights on the entire elementary wing, by Rooms#15, 18, 30, across from #23, 30 and Centerstone guidance, in the gym and cafeteria and throughout.  Periodic testing is required.  NFPA 101: 7.9.3
2. Replace ceiling tile in Room#18.  NFPA 101: 8.3.4.1
3. Replace the storage room door by Room#15.  There is a large square cut out of the center of the door.  Rooms or spaces used for storage shall be separated from the remainder of the building by fire barriers having a fire resistance rating of not less than 1 hour or protected by automatic extinguishing systems.  NFPA 101: 15.3.2.1
4. Service fire extinguisher by Room#7.  NFPA 10: 6.3.1
5. There shall be 3 ft. clearance around electrical panels (in office supply room).  NFPA 70: 110-26 (b)
6. There shall be one window that is clear, unobstructed, and operable at all times for emergency rescue (Room#29).  NFPA 101 15.2.11.1
2010/11: Closed
11/12: Newly renovated

MAPLEWOOD FRESHMAN ACADEMY (MCGAVOCK PIKE)
2009: 1. Repair or replace exit sign by lower level elevator.  NFPA 101: 7.10.9.1
2010/11:  Not open
2011/12: Not open

MAPLEWOOD HIGH (WALTON LANE)
2009:
1. Service emergency lights in the library, near the 2nd floor vending machines, by #216 and throughout.  NFPA 101: 7.9.3
2. Seal penetrations in the stairwells and in the elevator room (Vocational building).   NFPA 101: 8.3.5.1*
3. Replace ceiling tile throughout.  NFPA 101: 8.3.4.1
4. Several fire doors were propped open because of broken magnetic devices.  Repair hardware or keep doors closed.  NFPA 101: 7.2.1.8.1
5. Pizza oven in Culinary Arts shall be provided with suppression system coverage.  Also kitchen hoods shall cover appliances completely.  NFPA 96: 10.1.2
2010/11:
1. Service exit lights by #218 and throughout.  NFPA 101: 7.2.12.3.5.2
2011/12:
1. Fire alarm panel in trouble.  NFPA 101: 10.2.1.2
2. Service emergency lights in the kitchen and auditorium.  Periodic testing is required.  NFPA 101: 7.9.3
3. Service fire extinguishers the boiler room and large gym.  NFPA 10: 6.3.1
4. Sprinkler room shall have a spare cabinet with six spare sprinklers and a sprinkler wrench.  NFPA 13: 6.2.9.1 and NFPA 13: 6.2.9.6
5. Repair fire doors in breezeway next to the main office that goes to the gym.  They are "sticking" on the floor and unable to close properly.  NFPA 101: 7.2.1.8.1*
6. Egress corridors shall not be blocked.  Remove "theater" props from the back stage corridor.  NFPA 101: 7.1.10.1*

MARGARET ALLEN MIDDLE
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service emergency light by the mechanical room outside of the cafeteria and in the rear of the kitchen.  Periodic testing is required. NFPA 101: 7.9.3
2010/11: NONE
2011/12:
1. The fire alarm panel is in trouble mode. Repair immediately.  NFPA 72: 10.2.1.2 
2. Service emergency lights. There were several not working throughout the building.  NFPA 101: 7.9.3
3. There shall be no storage in electrical and mechanical rooms (#144F).  NFPA 70-110.26

MARTHA VAUGHT MIDDLE
2009: Closed
2010/11: Closed
11/12: Closed

MARTIN LUTHER KING MAGNET SCHOOL
2009:
1. Service emergency lights in the southeast stairwell, auditorium, by#207 and in the cafeteria serving line.  Periodic testing is required. NFPA 101: 7.9.3
2. Exits shall remain free and clear of obstructions.  Cars shall not be parked so closely outside exit doors (soccer field side).  NFPA 101: 7.1.10
3. Lawn equipment (and other fuel powered equipment) shall not be stored inside the building.  NFPA 1: 10.19.7
4. Flammable liquids (including aerosols) shall be stored properly (in a flammable liquids cabinet).  NFPA 1: 34.4.4.1
5. Adjust stairwell door (southwest corner of the new wing) so that it no longer "sticks" in the open position.  NFPA 101: 7.2.1.8.1*
6. Repair large "hole" in the lower level stairwell wall nearest room#6 in the new wing.  NFPA 101: 8.3.5.1*
7. Service Class K fire extinguisher in the kitchen and the fire extinguisher in the small gym's mechanical room.  NFPA 10: 6.3.1
2010/11:
1. Service emergency lights across from #215, next to #212 and 205, in the serving line, by the SRO office and throughout as needed.  NFPA 101: 7.9.3
2. Seal penetrations in the mechanical room by the lower level elevator, by #300 and by #215.  NFPA 101: 8.4.4.1
3. There shall be no storage in mechanical (gym) , electrical nor elevator rooms.  IFC 315.2.3
4. There shall be no storage in stairwells (across from backstage area, by #15 in new wing, and also remove the bicycle).  NFPA 101: 7.2.2.5.3*
5. Repair stairwell door (across from #113) so that it does not "stick" on floor.  NFPA 101: 7.2.1.8.1*
6. Stairwells (by #108 and 315) shall be constructed to maintain fire and smoke barriers.  Seal spaces above doors.  NFPA 101: 8.3.3.1 
Exits shall remain free and clear for use (in room#18NW).  Also, rearrange chairs (by SRO office)so that the exit is not blocked.  NFPA 101: 7.1.10.1
2011/12:
1 .Service emergency lights in auditorium (courtyard side), by #106 and in serving line area.  NFPA 101: 7.9.2.3*
2. Seal penetrations in corridor outside auditorium, in stairwell near #15NW, outside men's restroom by #203, by 303, 308, corridor outside gym.  NFPA 101: 8.3.4.1
3. Replace missing door hardware #202 in stairwell.  NFPA 101: 7.2.1.9.2
4 .Kitchen oven shall have a nozzle for coverage.  NFPA 96
5. Sprinkler system shall be serviced annually.  NFPA 25: 5.2.1.1

MCCANN ALTERNATIVE CENTER
2009:
1. Seal penetrations and openings in the corridor outside of the office, outside the Guidance Counselor's office, copy room and by #203.  NFPA 101: 8.3.5.6.1
*It is recommended that the old emergency lights that are not working in the cafeteria be removed since emergency lighting is sufficiently provided by the newer ones.
2010/11:
1. Seal penetrations in office and seal open grates in east wing stairwell to maintain separation.  NFPA 101: 8.4.4.1
2. Service emergency exit light by east wing stairwell. (Remove old one near kitchen – non working)  NFPA 101: 7.9.3
2011/12:
1. Service emergency lights in gym.  NFPA 101: 7.9.3
2. Seal "vent" like openings at the top of walls (ex. outside of main office) to maintain fire barrier.  NFPA 101: 8.3.4.1
3. Egress corridor doors shall not be propped open (including gym hall doors and main office door).  NFPA 101: 7.2.1.8.1*

MCGAVOCK ELEMENTARY
2009:
1. Service emergency lights next to Room #10, 14, 21, in the stairwell near #14, and in the restrooms by #7.  Periodic testing is required.  NFPA 101: 7.9.3
2. Seal penetrations in mechanical room near #20.  NFPA 101: 8.3.5.1*
3. Service exit signs in classrooms #21, 22, and 23.
4. Classroom (and egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
2010/11:
1. Service exit sign in classroom #23.  NFPA 101: 7.10.9.1
2. Classroom (& egress corridor) doors shall not be propped open.  Remove stoppers.  NFPA 101: 7.2.1.8.1*
3. There shall be no storage in stairwell.  This is unusable space.  Remove sandbox, chairs, etc. (by #21)  NFPA 101: 7.2.2.5.3*
2011/12:
1. Classroom (and egress corridor) doors shall not be propped open ( including main office and library), remove door stoppers and wedges.  NFPA 101: 7.2.1.8.1*
2. Artwork and teaching material shall not cover more than 20% of walls.  NFPA 101: 15.7.4.3
3. Service emergency light by room #10.  NFPA 101: 7.9.2.3*
4. There shall be no storage in stairwell (by room # 21).  NFPA 101: 7.2.2.5.3*

MCGAVOCK HIGH
2009:
1. Seal penetrations in the hallway near #120, in the corridor to the auxiliary gym & and in Room#115.   NFPA 101: 8.3.4.1
2. Kitchen grease filters shall be installed properly (vertically).  NFPA 96: 6.2.1.5
3. Commercial kitchen hood suppression system shall be serviced every 6 months.  NFPA 96: 11.2.1
4. Replace missing fire extinguisher just before the Vocational wing.  NFPA 10: 5.2.1
2010/11:
1. Fire alarm panel in trouble.  Repair immediately.  NFPA 101: 4.6.12.1
2. Seal penetrations at rear of auditorium by exit and throughout.  NFPA 101: 8.3.5.1
3. Service and tag fire extinguisher next to restrooms in Vocational hall, across from Art A, and by #251. NFPA 10: 6.3.1
4 Repair broken "vents" at bottom of doors in Vocational Hall so that door is solid. NFPA 101: 8.3.4.1
5 Provide a door closer for #124 (Voc), Autobody and closet door next to Autobody, and #151. NFPA 101: 8.4.4.1
6. Remove excess storage from the boiler room and mechanical room in Music department. NFPA 1: 10.19.5.1
7. Grills shall not be stored in building (boiler room). IFC 308.3.1.1
8. Flammable liquids shall be stored properly.  Remove from boiler room. NFPA 30
9. Service and provide emergency lights for Auto Collision Repair Service, band room, next Choral room, by #226a and by #223. NFPA 101: 7.9.3
10. Repair whole in door (#140). NFPA 101: 8.4.4.1
11. Repair classroom door so that it does not "stick" in open position (#155).  NFPA 101: 7.2.1.8.1*
12. Classroom (and egress corridor) doors shall not be propped open (throughout bldg).  NFPA 101: 7.2.1.8.1*
13. Clothes dryer in cosmetology shall be vented to the outside. NFPA 211: 10.7.3.3
14. Windows in corridor (health class) not rated.  NFPA 101: 8.4.4.1
15. Smoke detector in front of elevator.  NFPA 72: 5-7-4-1
2011/12:
1. Classroom (& egress) doors shall not be propped open (library).  NFPA 101: 7.2.1.8.1*
2. Classroom doors shall be solid without grates.  NFPA 101: 8.3.5.1
3. Replace "lock" hardware on storage door across from #251.  NFPA 101: 7.2.1.9.2 (5)
4. Re-evaluate emergency lighting (especially upper level).  NFPA 101: 7.9.2.3*
5. Service emergency lights in gyms (repair and/or replace as needed).  NFPA 101: 7.9.3
6. Provide smoke detection throughout to meet the exception for no manual pull station.  NFPA 72: 5.7.4.1

MCKISSACK MIDDLE
2009: Closed
2010/11: Closed
2011/12:
1. Service emergency lights in stair throughout the building as needed including Boys and Girls Club/YMCA.  NFPA 101: 7.9.3
2. Repair exit sign in the gym.  NFPA 101: 7.10.9.1
3. Remove excess storage from the mechanical room (by lower level elevator).  IFC 315.2.3

MCMURRAY MIDDLE
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service emergency lights in the library entry, across from 222C, nearest 124B and throughout as needed.  Periodic testing is required. NFPA 101: 7.9.3
3. Provide emergency light for upper level stairwell by 7th grade.  NFPA 101: 7.9.2.2
4. Seal penetrations in the custodian closet across from 122C.  NFPA 101: 8.3.4.1
5. There shall be no less than one window in each classroom (Room #400) that remains clear, unobstructed and operable for emergency rescue at all times.  NFPA 101: 15.2.11.1
6. Classroom doors shall not be propped open (#110, 108 and 111).  NFPA 101: 7.2.1.8.1
7. There shall be no combustibles stored in the boiler room.  NFPA 1: 10.19.5.1
2010/11:
1. Repair door closer room #103.  NFPA 101: 7.2.1.8
2. Service emergency light in cafeteria near serving line.  NFPA 101: 7.9.3
3. There shall be no storage in stairwells (chairs in several locations).  NFPA 101: 7.2.2.5.3*
4. Service exit signs in library and main lobby.  They shall be illuminated at all times.  NFPA 101: 7.10.9.1
2011/12:
1. Service emergency lights nearest room #103, 120, 205, and the girls locker room.  Repair one emergency light in the small gym. Periodic testing is required.  NFPA 101: 7.9.3
2. Service exit signs in the front lobby.  NFPA 101: 7.10.9.1*

MEIGS MIDDLE
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service emergency lights in the stairwell nearest the gym and throughout as needed.  Periodic testing is required. NFPA 101: 7.9.3
3. Seal penetrations (large opening in ceiling) in the stairwell nearest the gym.  NFPA 101: 8.3.4.1
4. Relocate smoke detectors (by Room#128, in the Guidance office, and in the cafeteria near tray disposals) so that they are not located in a direct airflow nor closer than 3 ft. where airflow prevents operation of the detectors.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11:
1. Fire alarm panel is in trouble.  Repair immediately.  NFPA 101: 4.6.12.1
2. Repair large square cut out of ceiling in gym lobby area.  NFPA 101: 8.4.2
2011/12:
1. Service exit sign in stairwell nearest gym.  NFPA 101: 7.10.9.1
2. Service fire extinguishers throughout.  NFPA 10: 6.3.1

MNPS MIDDLE HIGH
2009: NONE
2010/11: NONE
11/12: NONE

MT VIEW ELEMENTARY
2009:
1. Service emergency lights by #003 and near the elevator.  Periodic testing is required.  NFPA 101: 7.9.3
2. There shall be no storage in stairwells.  Remove plant, chairs and desk from lower level stairwells).   NFPA 101: 7.2.2.5.3*
3. Stairwell doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
2010/11:
1. Service emergency lights in front of the Tae Kwon Do pictures, in the stairwell by #123 and in the stairwell across from the upper level elevator.  Periodic testing is required.  NFPA 101: 7.9.3
2011/12:
1. Service emergency lights outside social worker, in gym, in stairwell, by rooms 123, 108 & 015, by workroom C, by photo collage,  and throughout.  NFPA 101: 7.9.3
2. There shall be no storage in stairwell (remove plants).  NFPA 101: 7.2.2.5.3*

MURRELL SCHOOL
2009:
1. Seal penetrations inside and outside the gym.  NFPA 101: 8.3.5.1*
2. There shall be no storage in stairwells (across from the elevator).  NFPA 101: 7.2.2.5.3.2
3. Service emergency lights in the cafeteria and across from Rooms#10 and #20.  Periodic testing is required.  NFPA 101: 7.9.3
4. There shall be no storage in the boiler room. NFPA 1: 10.19.5.1
2010/11:
1. Service exit signs by Support Services, in gym, outside and in cafeteria and main entrance.  NFPA 101: 7.10.9.1
2. Service emergency lights by Support Services, in gym, in cafeteria, outside gym and by #4.  NFPA 101: 7.9.3
3. Seal penetrations outside main gym doors.  NFPA 101: 8.3.5.1*
4. Repair stairwell door by elevator, on upper level so that it does not stick and stay open.  NFPA 101: 7.2.1.8.1*
2011/12:
1. Service emergency lights across support services, gym, cafeteria, and near room #14.  NFPA 101: 7.9.2.3*
2. Service exit sign in corridor outside cafeteria, in cafeteria, across from class #10, 15 and throughout.  NFPA 101: 7.2.12.3.5.2

NAPIER ENHANCED OPTION SCHOOL ELEMENTARY
2009: NONE
2010/11:
1. Fire alarm panel (system) in trouble mode.  Repair immediately.  NFPA 72: 10.2.1.2
2. Replace missing ceiling tile in workroom across from #114.  NFPA 101: 8.4.2
3. Gym for school use shall be connected to school fire alarm system.  NFPA 101: 15.3.4.1.1
4. Exit from gym shall not be padlocked.  NFPA 101: 7.1.10.1*
5. Emergency lights in gym shall be serviced.  NFPA 101: 7.9.3
2011/12:
1. There shall be a wrench in the spare sprinkler box in sprinkler room.  NFPA 13: 6.2.9.6
2. Repair four hour rated wall between gym and school.  There shall be no penetrations.  NFPA 101: 8.3.5.1*

NASHVILLE BIG PICTURE HIGH
2009:
1. Service emergency lights across from the lower level elevator, in the stairwell by #108, in the library and in the boys restroom across from #143.  Periodic testing is required.  NFPA 101: 7.9.3
2. There shall be no storage in stairwells (across from #211).  NFPA 101: 7.2.2.5.3*
3. Service kitchen suppression system every 6 months.  NFPA 96: 11.2.1
4. Relocate the smoke detectors so that they are not located within 3 ft. of an air duct.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11:
1. Service emergency lights in the stairwell by #211, in the cafeteria, and in the gym.  Periodic testing is required.  NFPA 101: 7.9.3
2. Smoke detectors shall not be located within 3ft. of an air diffuser (#73 by the cafeteria).  NFPA 72: 5.7.4.1
2011/12:
1. Fire alarm panel in trouble. Repair immediately.  NFPA 101: 4.6.12.1
2. Service emergency light by room 103.  NFPA 101: 7.9.3
3. Stairwell door shall not be propped open.  Repair magnetic hold device (middle stairs front hall).  NFPA 101: 7.2.1.9.2
4. Grills shall not be stored in sprinkler room.  IFC 308.3.1

NASHVILLE DIPLOMA
2009: Not open
2010/11:
1. Classroom (and egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
2. Classrooms shall have one window for rescue.  NFPA 101: 15.2.11.1.1
3. Service emergency lights in main office, office lobby and across from #113.  Periodic testing is required.  NFPA 101: 7.9.3
11/12: 4 violations

NASHVILLE SCHOOL OF THE ARTS
2009:
1. Fire drills shall be conducted monthly and documented.  NFPA 101: 15.7.2.2
2. Service exit signs by #07 and #11.  NFPA 1: 10.14.7
3. Grills are prohibited from storage within the building (mechanical/boiler room rear of kitchen). NFPA 1: 10.11.7
4. Open flame candles are prohibited from use inside the building.  NFPA 1: 10.14.7
2010/11:
1. Fire alarm panel in trouble mode.  Repair immediately.  NFPA 101: 4.6.12.1
2. Sprinkler head above deep fryers shall be clean and free of debris.  NFPA 25: 5.2.1.1.1
3. Service emergency lights in room #1, 2, 3, 4 and throughout.  NFPA 101: 7.9.3
11/12:
1. Service exit sign by Music studio, stage rear, middle of theater hall and throughout.  NFPA 101: 7.2.12.3.5.2
2. Replace missing ceiling tile throughout music area and by 31.  NFPA 101: 8.4.2
3. Kitchen hood sprinkler head shall be cleaned regularly.  NFPA 96: 11.2.1

NEELY'S BEND ELEMENTARY
2009:
1. Service emergency light at the top ramp of the 3rd grade hall and by #B-114.  Periodic testing is required.  NFPA 101: 7.9.3
2. Relocate smoke detector (bottom ramp of 3rd grade hall) so that it is not located in a direct airflow nor closer than 3 ft. where airflow prevents operation of the detector.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
3. Service fire extinguishers across from #B-116 and B-120.  NFPA 10: 6.3.4
2010/11:
1. There shall be no storage under stairwell (lower level by receiving).  NFPA 101: 7.2.2.5.3*
2011/12:
1. Service exit signs in the Art portable.  NFPA 101: 7.10.9.1

NEELY'S BEND MIDDLE
2009:
1. Service emergency lights outside the main office, outside the gym by guidance and near band room, by #122, 205, 209, & 217, by exit near boys locker room, and in stairwell and hall near the bookroom.  (Dark  brown ones throughout)  Periodic testing is required.  NFPA 101: 7.9.3
2. Service exit signs near the elevator (1st and 2nd level).  NFPA 101: 7.10.9.1
3. Repair Stair door #2 so that it closes completely.  NFPA 101: 7.2.1.8.1
4. Seal penetrations in and outside #215.  NFPA 101: 8.5.6.3
2010/11:
1. Fire alarm panel is in trouble mode.  Repair immediately.  NFPA 72: 10.2.1.2
2. Service emergency lights outside cafeteria by office, in cafeteria, across from #107, stairwell across from #02, and throughout.  NFPA 101: 7.9.3
3. Service exit signs on 1st and 2nd floor near elevator.  NFPA 101: 7.10.9.1
2011/12: NONE

NORMAN BINKLEY ELEMENTARY
2009: NONE
2010/11:
1. Service emergency lights in the kitchen serving line and across from the boiler room.  Periodic testing is required.  NFPA 101: 7.9.3
2. Seal penetrations in the kitchen by the freezers and in the boiler room.  NFPA 101: 8.3.5.1*
3. Classroom (& egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
2011/12:
1. Service emergency lights next to room 23 and across from room 22.  NFPA 101: 7.9.3
2. Classroom (& egress corridor) doors shall not be propped open including cafeteria serving line door.  NFPA 101: 7.2.1.8.1*

OLD CENTER ELEMENTARY
2009:
1. Stairwell doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
2. There shall be no storage in the elevator room.  NFPA 1: 10.19.5.1
2010/11:
1. There shall be no storage in stairwell (LL by elevator).  NFPA 101: 7.2.2.5.3*
2. Stairwell doors shall not be propped open (upper and lower levels by elevator).  NFPA 101: 7.2.1.8.1*
3. Fire alarm panel in trouble mode.  Repair immediately.  NFPA 72: 10.2.1.2
2011/12:
1. Seal penetration in stairwell by C#107.  NFPA 101: 8.4.4.1

OLIVER MIDDLE
2009:
1. Stairwells shall not be used for storage.  Remove items in stairwell across from #220 immediately.   NFPA 101: 7.2.2.5.3*
2. Service emergency lights in gym near restroom by scoreboard and by Band room.  Periodic testing is required.  NFPA 101: 7.9.3
2010/11:
1. Service emergency lights in the library, cafeteria, outside cafeteria and throughout.  NFPA 101: 7.9.3
2. Portable P-516 shall have one window for rescue. NFPA 101: 15.2.11.1.1
3. Stairwell door (lower level) shall not be propped.  Repair magnetic hold device or keep door closed. NFPA 101: 7.2.1.8.1*
4. Replace missing ceiling tile in electrical room (in upper boys restroom). NFPA 101: 8.4.2
2011/12:
1. Service emergency lights in the main office, outside the restroom by the gym and across from #211.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service and tag fire extinguisher in #213.  NFPA 10: 6.3.1
3. Extension cords shall not be used in place of permanent wiring.  IFC 605.5
4. There shall be a wrench in the sprinkler room.  NFPA 13: 6.2.9.6

OVERTON HIGH
2009:
1. Service emergency lights throughout.  Periodic testing is required. NFPA 101: 7.9.3
2. Service, repair or replace exit signs throughout.  NFPA 101: 7.10.9.1
3. There shall be no storage in the elevator room.  NFPA 1: 10.19.5.1
4. Replace missing ceiling tile in corridors and classrooms throughout.  NFPA 101: 8.3.4.1
5. Add hardware to stairwell doors so there is no longer a gap between them (by#126).  NFPA 101: 8.3.3.1
2010/11:
1. Fire alarm panel in trouble!  Repair immediately.  NFPA 101: 4.6.12.1
2. Service exit sign (small gym).  NFPA 101: 7.2.12.3.5.2
3. Service emergency lights by vending machines near auditorium, in cafeteria, by courtyard side and in main entry foyer.  NFPA 101: 7.9.3
2011/12:
1. Replace missing fire extinguishers in boy's locker room and by exit into locker room and service fire extinguisher by #102, 210, library, 248 and throughout.  NFPA 10: 6.3.1
2. Service emergency lights in stairwell across from #142 and by 303.  NFPA 101: 7.9.2.3*
3. Replace missing (or broken) ceiling tile in various areas throughout.  NFPA 101: 8.4.2
4. Service exit signs in rear of gym and baseball room.  NFPA 101: 7.2.12.3.5.2
5. There shall be a wrench in the spare sprinkler box in sprinkler room.  NFPA 13: 6.2.9.6
6. Exits shall not be blocked (computer class #307 and outside boiler room).  NFPA 101: 7.1.10.1*

PARAGON MILLS ELEMENTARY
2009:
1. Service emergency lights by #0018 and in the gym.  Periodic testing is required.  NFPA 101: 7.9.3
2. Classroom (and egress corridor) doors shall not be propped open.   NFPA 101: 7.2.1.8.1*
3. Service fire extinguisher next to the Centerstone Office.  NFPA 10: 6.3.1
2010/11:
1. Service emergency light in the girls restroom near #0015.  Periodic testing is required.  NFPA 101: 7.9.3
2. Replace ceiling tile in various areas to limit the spread of smoke and fire.  NFPA 101: 8.4.2
3. Classroom (and egress corridor) doors shall not be propped open (including library and offices).  Remove any door stoppers and wedges. NFPA 101: 7.2.1.8.1*
2011/12:
1.  Fire alarm panel in trouble.  (Metro maintenance was on-site repairing during inspection)  NFPA 72: 10.2.1.2
2. Classroom (and egress corridor) doors shall not be propped open including library, rooms# 5, 6, 7, 15 and throughout.  NFPA 101: 7.2.1.8.1*
3. Seal large penetrations in the boiler room.  NFPA 101: 8.3.5.1*

PARK AVENUE ELEMENTARY
2009:
1. Service emergency lights by #223, 225, 226, 227, in the kitchen, front foyer, and  copy room and on the long fall 5th grade.  Periodic testing is required.  NFPA 101: 7.9.3
2. Relocate the smoke detector (in two storage rooms near the elevator) so that it is not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11
1. Service emergency lights across from upper elevator, across from custodial office and throughout as needed.  NFPA 101: 7.9.3
2011/12:
1. Service emergency lights throughout. Periodic testing is required.  NFPA 101: 7.9.3
2. Service fire extinguisher in kitchen (Class K).  NFPA 10: 6.3.1
3. Sprinkler system shall be serviced annually (last serviced 3/11/2010).  NFPA 25: 5.2.1.1

PEARL-COHN FRESHMAN ACADEMY
2009:
1. Fire drills shall be conducted monthly and documented.  NFPA 101: 15.7.2.2
2. Relocate the smoke detector (near the exit outside the cafeteria) so that it is not located within 3 ft. of an air duct.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11:
1. Fire alarm panel in trouble mode.  Repair immediately.  4.6.12.1
2011/12: Closed

PEARL-COHN COMPREHENSIVE MAGNET HIGH
2009:
1. Service emergency lights by the 3rd floor boys restroom, by #106, in both gyms, in the Band room, outside Choir, throughout the auditorium and throughout as need.  NFPA 101: 7.9.3
2. Service exit signs in the small gym.  NFPA 101: 7.10.9.1
3. Candles (open flames) shall not be used.  NFPA 1: 10.1.5
2010/11:
1. Service emergency light outside auditorium and in auditorium by side exit, outside gym balcony, library and throughout.  NFPA 101: 7.9.3
2. Repair broken exit signs in main gym and small gym.  NFPA 101: 7.2.12.3.5.2
2011/12:
1. Fire drills shall be conducted monthly and documented.  NFPA 101: 15.7.2.2
2. Service emergency lights throughout.  Periodic testing is required.  NFPA 101: 7.9.3
3. Service fire extinguishers nearest room #121, 115 and throughout.  NFPA 10: 6.3
4. Replace missing or broken ceiling tile in various areas throughout.  NFPA 101: 8.4.2
5. Smoke detector shall not be located within 3 feet of an air diffuser (by back stair near #127).  NFPA 72: 5.7.4.1
6. Kitchen suppression system shall be serviced every 6 months.  NFPA 96: 11.2.1

PENNINGTON ELEMENTARY
2009:
1. Service or repair (already in progress) needed for emergency lights throughout the kindergarten hall.  Periodic testing is required.   NFPA 101: 7.9.3
2010/11:
1. Service exit signs by classroom #1 and at the main entry (back-up lighting).  NFPA 101: 7.10.9.1
2. Seal penetrations in the janitor's closet near #11.  NFPA 101: 8.3.5.1*
2011/12:
1. Service emergency lights in the boys and girls restooms nearest room#11.  NFPA 101: 7.9.3

PERCY PRIEST ELEMENTARY
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service and tag fire extinguisher in the cafeteria.  NFPA 10: 6.3.1
3. Seal penetrations in the boiler room.  NFPA 101: 8.3.5.1*
4. Classroom (and egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.2*
5. There shall be one window free and clear for rescue (Tiger Club portable).  NFPA 101: 15.2.11.1.1
2010/11:
1. Fire alarm panel in trouble.  Repair immediately.  NFPA 101: 4.6.12.1
2. Classroom and egress corridor doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
3. Service emergency lights by Room#3.  Periodic testing is required.  NFPA 101: 7.9.3
4. Service fire extinguisher by Room#11.  NFPA 10: 6.3.1
5. Artwork and learning materials shall not exceed 20% of wall (especially kindergarten area).  NFPA 101: 15.7.4.3 
6. Jackets and book bags in hallways (on hooks by Room #3 and by the gym) shall be stored in metal lockers.  NFPA 101: 15.7.4.2
2011/12:
1. Fire alarm panel in trouble mode.  Repair immediately.  NFPA 72: 10.2.1.2
2. Classroom (& egress corridor) doors shall not be propped open (including main office, room 14, 13, 9, 8, 7).  NFPA 101: 7.2.1.8.1*
3. Clothing and personal belongings shall not be stored in corridors unless in metal lockers. (by room 3, 4, 8, 9, 15).  NFPA 101: 14.7.4.2
4. Maintain 6 ft. corridor width in Kindergarten hall and by room 17.  NFPA 101: 14.2.3.2

ROBERT LILLARD ELEMENTARY/DESIGN SCHOOL
2009:
1. Provide a door closer for the secondary (accounting) office across from the library.  NFPA 101: 8.4.3.5
2010/11:
1. Fire alarm panel in trouble.   Repair immediately.  NFPA 101: 4.6.12.1
2. Service emergency light by Classroom #23.  Periodic testing is required.  NFPA 101: 7.9.3
3. Seal penetrations in the custodian office outside the cafeteria.  NFPA 101: 8.3.5.1*
2011/12: Now Lillard Design School
1.  Fire doors shall not be propped open (4 hour separation between old building and gym).  Repair magnetic hold-open devices or keep doors closed.  NFPA 101: 7.2.1.8.1*
2. Service emergency lights in the boys and girls restrooms by gym and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3

ROBERTSON ACADEMY
2009:
1. Service emergency lights by Room#4 and outside the front office.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service exit sign at the front entrance.  NFPA 101: 7.10.9.2
3. Seal penetrations above the door just outside the office.  NFPA 101: 8.3.5.1
2010/11: NONE
2011/12:
1. Service exit/emergency lights in rooms#6, #7 and by the Assembly room.  NFPA 101: 7.9.3

ROSE PARK MIDDLE
2009:
1. Service emergency lights near the blue stair, in the library, across from Rm#213 and throughout as needed.  Periodic testing is required. NFPA 101: 7.9.3
2. Seal penetrations inside the storage room near the office, outside the blue stair, in Rm#212, outside the bookroom near #112 and in the boiler room.  NFPA 101: 8.3.5.6.1
3. Relocate the exit sign across from Rm#204 so that it is visible from different angles.  NFPA 101: 7.10.2
4. The length or width of the building exceeds 300 ft and shall be subdivided into compartments by smoke partitions.   NFPA 101: 15.3.7.1
5. There shall be no storage in stairwells.  NFPA 101: 7.2.2.5.3*
6. Provide door closers for Music #103.  NFPA 101: 7.2.1.8.1
7. Repair horn strobe device in small gym.  NFPA 72: 7.3.5.2
2010/11:
1. Repair light fixture outside of gym so that wiring is not exposed.  NFPA 70
2. Seal penetrations in stairwell by #112 and in corridor by # 112.  NFPA 101: 8.3.5.1
2011/12:
1. Service emergency lights by upper level water fountain, gym, throughout the large gym, by #302, girls restroom by #309, boys restroom by #201 and throughout.  NFPA 101: 7.9.3

ROSEBANK ELEMENTARY
2009:
1. Service emergency lights in the stairwell by Music, near #125 and in the lobby by flag display.  Periodic testing is required.  NFPA 101: 7.9.3
2. Seal penetrations in custodian's closet in the hall near the back side of the caferteria.  NFPA 101: 8.3.4.1
2010/11:
1. Service emergency lights by #127, #125, in mechanical room, and by lower level elevator.  NFPA 101: 7.9.3
2. Classroom (& egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.1* 2011/12:
1. Service emergency lights by #126 and by #125, in stair by #127.  NFPA 101: 7.9.3
2. Service exit sign in cafeteria and end of kindergarten/1st grade hall and by room 002.  NFPA 101: 7.10.9.1
3. Seal penetrations in library IT room.  NFPA 101: 8.3.4.1

ROSS ELEMENTARY
2009:
1. Service emergency lights outside restrooms by the gym.  Periodic testing is required.   NFPA 101: 7.9.3
2. Relocate smoke detector (in front office and by Room#11) so that it is not located in a direct airflow nor closer than 3 ft.  where airflow prevents operation of the detector.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
3. Replace missing ceiling tile by Room#11 to limit the spread of fire and smoke.  NFPA 101: 8.3.4.1
2010/11: NONE
2011/12:
1. Service emergency lights by rooms# 24 and 18, outside the library and throughout as needed. (older models)  NFPA 101: 7.9.3

RUBY MAJOR ELEMENTARY
2009:
1. Service emergency lights in the cafeteria, outside the main office and by #103.  Periodic testing is required.  NFPA 101: 7.9.3
2010/11:
1. Service emergency lights in the kitchen near the ice machine.  Periodic testing is required.  NFPA 101: 7.9.3
2. Relocate smoke detectors (at exit by central receiving and by #170) so that they are not closer than 3 ft. to an air diffuser.  NFPA 72: 5.7.4.1
3. There shall be no storage within 18 inches of sprinkler heads (storage room across from #165).  NFPA 13: 8.5.6.1
2011/12: NONE

SHAYNE ELEMENTARY
2009:
1. Stairwells shall not be used for storage.  Remove items in stairwell across from #164 immediately.   NFPA 101: 7.2.2.5.3*
2. Artwork shall not exceed 50% of walls (kindergarten hall).  Continue to monitor this throughout.  NFPA 101: 15.7.4.3
2010/11
1. Service emergency lights outside cafeteria and in kitchen at entrance. NFPA 101: 7.9.3
2. Repair openings (cut) in ceiling in storage room by sprinkler room. NFPA 101: 8.4.2
2011/12:
1. Service emergency lights in the kitchen, by #157 and in the girls' restroom by #157.  Periodic testing is required.  NFPA 101: 7.9.3
2. There shall be one window free and clear for rescue (P-11).  Rearrange bookcase & shades in other Portables so that the window opens freely.  NFPA 101: 15.2.11.1.1

SHWAB  ELEMENTARY
2009:
1. Service emergency lights across from custodian office, outside Art, and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2010/11:
1. Service emergency lights across from #242, #250, and #216.  Periodic testing is required.  NFPA 101: 7.9.3
2. Replace ceiling tile in various areas throughout.  NFPA 101: 8.4.2
2011/12:
1. Smoke detector shall be no closer than 3ft to an air diffuser (near exit by gym).  Also, remount smoke detector by #250.  NFPA 72: 5.7.4.1
2. Replace ceiling tile by #226.  NFPA 101: 8.4.2

SMITHSON CRAIGHEAD ACADEMY
2009: NONE
2010/11: NONE
2011/12:
1. Service emergency lights throughout.  NFPA 101: 7.9.2.3
2. Sprinkler system shall be serviced.  NFPA 25: 5.2.1.1

S, MITHSON CRAIGHEAD MID, DLE
2009:
1. Service all fire extinguishers throughout the building (expiration 6/2007).  NFPA 10: 6.3.1
2. Seal penetrations  outside Rm#25 and outside the main office.  NFPA 101: 8.3.5.1*
3. Classroom (and egress corridor) doors shall not be left in , the open position. Repair door closers throughout so that the doors close automatically.  NFPA 101: 7.2.12.3.4.3
4. Replace missing fire extinguisher across from , Rm#25.  NF, PA 10: 5.2.1
5. There shall be no storage in the boiler room.&nb, sp; N, FPA 1: 10.19.5.1
2010/11:
1. Seal penetrations in custodian closet next to #116, in corridor by#24 and in the lower level storage room.  NFPA 101: 8.4.4.1
2. Classroom (and egress corridor) doors shall not, be propped open.  NFPA 101: 7.2.1.8.1*
3. Provide (or repair) d, oor closing devices for corridor doors including #116, 133, 135, 136, AV room, Music, #105, 108, 109, 110, 111, and library.  NFPA 101: 7.2.1.8
2011/12: NONE

SPECTRUM ACADEMY
2009: Not open yet
2010/11
1. Fire alarm system shall be serviced and tagged annually.  , NFPA 72: 10.4.2.2 and IFC 901.7.3
2. Provide fire extinguishers.  NFPA 10: 1.5.3        (corrected 1/27/11)
3. There shall be a manual pull station within 5 ft of every exit.  NFPA 72: 5.13.6
4. Provide door closers for corridor doors.  NFPA 101: 7.2.1.8
5. Classrooms shall ha, ve one outside window that remains unobstructed, a, nd operable for emergency rescue at all times. R, emove nails immediately.  NFPA 101: 15.2.11.1.1       (corrected 1/27/11)
6. Seal penetrations by #106 and throughout corridor.  NF, PA 101: 8.4.4.1
2011/12: Closed

STANFORD SCHOOL
2009:
1. Relocate smoke detector (by Rm#111) so that it is not located in a direct airflow nor closer than 3 ft.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11
1. Service fire extinguisher in the closet next to the teacher workroom by #153.  NFPA 10: 6.3.1
2. Relocate smoke detector so that it is not closer than 3 ft. to an air diffuser.  NFPA 72: 5.7.4.1
2011/12:
1. There shall be a wrench in sprinkler room.  NFPA 13: 6.2.9.6
2. Replace missing ceiling tile in custodian office.  NFPA 101: 8.4.2

STRATFORD HIGH

2009:
1. Fire alarm panel in trouble mode.  Repair within 24 hours.  NFPA 101: 4.6.12.1
2. Service emergency lights in both gyms, by #1002, 1007, 1024, and 1046, outside Band room, in the library, in stairwells, in the auditorium lobby and throughout.  NFPA 101: 7.9.3
3. There shall be no storage of combustibles in the boiler room.  NFPA 1: 10.19.5.1
4. Grills (in Auto Mechanics) shall not be stored in the building.  NFPA 1: 10.11.7
5. Gates from the courtyard by Cosmetology shall not be chained during normal operating hours.  NFPA 101: 7.1.10
2010/11
1. Service emergency light in gym, foyer towards bank, library, weight room and throughout.  NFPA 101: 7.9.3
2. Replace exit sign going toward band.  NFPA 101: 7.10.1.2*
3. Replace missing ceiling tile throughout.  NFPA 101: 8.4.2
4. Exit shall be reliable (Library rear exit).  Remove chains on ground level for exit.  NFPA 101: 7.1.10.1*
2011/12:
1. Service emergency lights in library, by 2014, across from stair 2020, in boys & girls locker rooms and throughout. Periodic testing is required.  NFPA 101: 7.9.3
2. Service fire extinguishers throughout including Class K in kitchen.  NFPA 10: 6.3.1
3. Replace ceiling tile on lower level (near#02)  and in various area throughout.  NFPA 101: 8.4.2
4. Remove excess storage from mechanical room by auditorium.  IFC 315.2.3
5. Sprinkler system shall be serviced annually (last serviced 3/3/2011).  NFPA 25: 5.2.1.1

STRATTON ELEMENTARY
2009: NONE
2010/11
1. Service emergency lights by mechanical room #193 and by Guidance. NFPA 101: 7.9.3
2011/12:
1. Service emergency lights nearest room #146.  NFPA 101: 7.9.3
2. Extension cords shall not be used in place of permanent wiring (room #144) – add outlets if necessary. IFC 605.5
3. There shall be a wrench in the spare sprinkler box in sprinkler room.  NFPA 101: 13:6.2.9.6

SYLVAN PARK ELEMENTARY
2009:
1. Service emergency lights by the boiler room, auditorium and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
2. Several doors throughout were secured in the open position. Classroom and egress corridor doors shall not be propped open. Remove door stoppers and wedges.  (non-sprinklered area)  NFPA 101: 7.2.1.8.2
3. Classrooms shall have one window free and clear for rescue. (non-sprinklered area)  NFPA 101: 15.2.11.1.1
4. There shall be no storage in stairwells.  Remove play equipment across from #106.  NFPA 101: 7.2.2.5.3.2
2010/11:
1. Classroom and egress corridor doors shall not be propped open. Remove door stoppers and wedges.  (non-sprinklered area)  NFPA 101: 7.2.1.8.1*
2. Service emergency lights in the 2nd floor girls restroom, outside the restroom towards elevator and throughout as needed.  Periodic testing is required.  NFPA 101: 7.9.3
3. There shall be no storage in stairwells.  Remove play equipment and items across from #106 items, in the lower level stair by Music, and in the cafeteria stair.  NFPA 101: 7.2.2.5.3*
4. Relocate smoke detector (by the 2nd floor elevator) so that it is no closer than 3 ft. to an air diffuser.  NFPA 72: 5.7.4.1
5. Seal penetrations in the custodian closet across from PNA aftercare and in the mechanical room by #101.  NFPA 101: 8.3.5.1*
6. Provide a door closer for the Clinic.  NFPA 101: 7.2.1.8
7 Jackets and sweaters in hallways shall be stored in metal lockers.  NFPA 101: 15.7.4.2
2011/12:
1. Fire alarm panel in trouble.  Repair immediately.  NFPA 72: 10.2.1.2
2. Service emergency lights in front foyer, outside auditorium, by cafeteria, outside serving line, 2nd floor girls' restroom, by upper level elevator and throughout the building.  NFPA 101: 7.9.3
3. Classroom (& egress corridor) doors shall not be propped open. (1st floor resource room, 317, 308, 306, 309, 307, 302, including main office and throughout building).  NFPA 101: 7.2.1.8.1*
4. There shall be no storage in the stairwells throughout building (across from room 106. going to Kindergarten, next to PE storage and from the cafeteria).  NFPA 101: 7.2.2.5.3*
5. Stairwell door shall not be propped (going to Kindergarten).  NFPA 101: 7.2.1.8.1*
6. Repair hole over door in kiln room.  NFPA 101: 8.3.4.1

THE ADADEMY AT HICKORY HOLLOW
2009: N/A
2010/11:  N/A
11/12: NONE

THOMAS EDISON ELEMENTARY
2009:
1. Stairwells shall not be used for storage.  Remove items in stairwell across from #219 immediately.   NFPA 101: 7.2.2.5.3*
2010/11: NONE
11/12: NONE

THURGOOD MARSHALL MIDDLE
2009:
1. Service or repair the emergency lights for the entire 5th grade hall and across from Locker #605 on the 8th grade hall.  Periodic testing is required.  NFPA 101: 7.9.3
2010/11:
1. Service the fire extinguisher by #219.  NFPA 10: 6.3.1
2011/12:
1. Service emergency lights in the gym (external side) and  6th grade boys restroom.  NFPA 101: 7.9.3
2. There shall be no storage in the stairwell nearest room#129.  Remove tables and chairs in stair#3 and by room#129.  NFPA 101: 7.2.2.5.3*
3. Seal penetrations in stairwell nearest room#129.  NFPA  101: 8.4.4.1

TOM JOY ELEMENTARY
2009:
1. Service emergency light by Rm#126.  Periodic testing is required. NFPA 101: 7.9.3
2. Relocate the smoke detector by the restrooms at the beginning of the long yellow halll so that it is not located within 3 ft. of an air duct.  NFPA 72: 5.7.4.1 (A-5.7.4.1)
2010/11: NONE
2011/12:
1. Service emergency lights by rooms #116, 132 and 148.  NFPA 101: 7.9.3
2. There shall be six (6) spare sprinkler heads in the spare box in the sprinkler room.  NFPA 13: 6.2.9.1
3. There shall be a wrench in sprinkler room.  NFPA 13: 6.2.9.6

TULIP GROVE ELEMENTARY
2009:
1. Service emergency light next to Room #207.  Periodic testing is required.   NFPA 101: 7.9.3
2010/11:
1. Service emergency lights across from #306, #107, #108, and by bookroom.  NFPA 101: 7.9.3
2011/12:
1. Service emergency lights by Bookstore and across from room #103 and 210.  NFPA 101: 7.9.2.3*

TUSCULUM ELEMENTARY
2009:
1. Provide door closers for classrooms and doors in the library corridor inclusing Rm#2 through #15.  Also, classroom doors shall not be propped open (Rm#24).    NFPA 101: 7.2.1.8.1 
2010/11:
1. Repair door so that it does not "stick" on the floor. NFPA 101: 7.2.1.8.1*
2. Service emergency lights between 3rd and 4th hall and gym, boys restroom by gym and throughout. NFPA 101: 7.9.3
3. Classrooms shall have one window for rescue including portables. NFPA 101: 15.2.11.1.1
4. Provide a door closer for the Assistant Principal's office door. NFPA 101: 7.2.1.8
2011/12:
1. There shall be a manual pull station within five (5) feet of exits (by room #27, #35, main entry, and exits at ramp in front of main entrance).  NFPA 72: 5.13.6
2. Service emergency lights in gym (at entrance), ramp to gym, and girls' restroom by gym.  NFPA 101: 7.9.3

TWO RIVERS MIDDLE
2009:
1. Several emergency lights were not working. Service emergency lights throughout.  Periodic testing is required.  NFPA 101: 7.9.3
2. Several doors throughout were secured in the open position. Classroom and egress corridor doors shall not be propped open.   NFPA 101: 7.2.1.8.2
3. Seal penetrations in the basement stairwell.  NFPA 101: 8.3.5.1*
4. There shall be no storage in stairwells (middle stair across from cafeteria).  NFPA 101: 7.2.2.5.3.2
2010/11:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Service emergency lights in stairways next to #209, 131, and 127, in the hall by #127 and 123,  in the cafeteria and throughout.  Periodic testing is required.  NFPA 101: 7.9.3
3. Seal penetrations in the janitor's closet across from #129 and in the Music room.  NFPA 101: 8.3.5.1*
2011/12:
1. Service emergency light in the small gym.  Periodic testing is required.  NFPA 101: 7.9.3
2. Classroom (and egress corridor) doors shall not be propped open (throughout).  NFPA 101: 7.2.1.8.1*
3. There shall be no storage in stairwells.  Remove boxes by #131 and dollies, etc. across from the cafeteria.  NFPA 101: 7.2.2.5.3*
4. Seal penetrations above #130, in the stairwell by #127 and outside the Band room.  NFPA 101: 8.3.5.1*
5. Relocate "coat rack" (room#130) so that the doorway is clear.  NFPA 101: 7.1.10.1*
6. Repair/adjust door #130 so that the door closes completely.  NFPA 101: 7.2.1.8.1*
7. Replace/repair (glass) opening in the concessions stand door.  NFPA 101: 8.4.4.1

UNA ELEMENTARY
2009:
1. Seal penetrations in the boiler room.  NFPA 101: 8.3.4.1
2. There shall be no storage within exit enclosures, including under stairs. Remove furnitutre and other items from stairwell.  NFPA 101: 7.2.2.5.3*
3. Service exit sign by Rm#125, in the rear of kitchen and just outside of the library.        NFPA 101: 7.10.9.1
4. Service emergency lights in the long hall to the gym, in the stairwell near the cafeteria, and by Room #131.  Periodic testing is required. NFPA 101: 7.9.3
2010/11:
1 There shall be one window free and clear for rescue. (Portable #4).  NFPA 101: 15.2.11.1.1
2. Kitchen hood filters shall be installed properly.   NFPA 96: 6.2.5
2011/12:
1. There shall be one window for rescue (Portables #2 and 3).  NFPA 101: 15.2.11.1.1
2. There shall be no storage in stairwell.  Remove bench and plants.  NFPA 101: 7.2.2.5.3*

W.A. BASS MIDDLE
2009:
1. The fire alarm system was in trouble mode on the panel instead of normal mode.  This repair shall always be corrected within 24 hours.  NFPA 101: 4.6.12.1
2. Classrooms shall have one window for rescue (blocked in room#206).  This also includes classrooms that open into the courtyard (rooms #102, 104, 108, 110).  NFPA 101: 15.2.11.1.1
3. Service emergency lights across from the concessions, in both gyms and in the Music room.  Periodic testing is required.  NFPA 101: 7.9.3
4. Service exit signs in the auditorium.  NFPA 101: 7.10.9.1
5. Repair stairwell door next to rm#107 so that it is no longer "sticking" on the wall and closes completely.  NFPA 101: 7.2.1.8.1*
6. Add pull stations to classrooms in the Computer Lab portable.  Manual fire alarm boxes shall be located within 5 ft of the exit doorway opening at each exit.  NFPA 72: 13.6
2010/11:
1. Fire alarm panel in trouble mode.  Repair immediately.  NFPA 101: 4.6.12.1
2. Service emergency lights by Art, in Music, outside cafeteria, by #112, in locker rooms and throughout.  Periodic testing is required.  NFPA 101: 7.9.3
3. Service exit sign by Art, in small and large gyms.  NFPA 101: 7.10.9.1
4. Classrooms shall have one window for rescue (in courtyard: #102, 104, 108, 110).  NFPA 101: 15.2.11.1.1
5. Grills shall not be stored in the building (in storage room by cafeteria).  NFPA 1: 10.11.7
6. Gas-fueled lawn equipment shall not be stored in the building.  IFC 313.1
2011/12: Closed

WARNER ELEMENTARY
2009:
1. Relocate the smoke detector in the basement elevator lobby, in front of Room#105, and near Room#103 so that they are not located where airflow prevents operation and should not be located in a direct airflow nor closer than 3 ft.   NFPA 72: 5.7.4.1 (A-5.7.4.1)
2. There shall be no storage in stairwells (across from Room #102).  Remove cots.  NFPA 101: 7.2.2.5.3*
2010/11:
1. There shall be no storage in stairwells. (by #317, both gym stairs, back of gym, upper and lower).  NFPA 101: 7.2.2.5.3*
2. Smoke detector shall be no closer than 3 feet to an air diffuser (by #111).  NFPA 72: 5.7.4.1
3. Service emergency light in stairs (back of gym).  NFPA 101: 7.9.3
2011/12:
1. Service emergency lights in the cafeteria, gym and auditorium.  Periodic testing is required.  NFPA 101: 7.9.3
2. Service fire extinguishers throughout including Class K in the kitchen.  NFPA 10: 6.3.1
3. Sprinkler room shall have a spare cabinet with six spare sprinklers and a sprinkler wrench.  NFPA 13: 6.2.9.1 and NFPA 13: 6.2.9.6
4. Seal penetrations in the stairwell next to the first floor elevator.  NFPA 101: 8.3.5.1

WEST END MIDDLE
2009: NONE
2010/11:
1. Service or repair emergency lights throughout.  There were several not working on the 3rd floor, in stairwells, and other areas throughout the building.  Periodic testing is required.  NFPA 101: 7.9.3
2. Gas-fueled lawn equipment shall not be stored in the building (in the hall outside the elevator room).  IFC 313.1
2011/12:
1. Service emergency lights by room #113 and 311, in the upper level auditorium, by the basement elevator, and throughout the building as needed.  NFPA 101: 7.9.3
2. Stairwell door shall not be wedged open (by room#300).  Repair magnetici hold open device or keep door closed.  NFPA 101: 7.2.1.8.1*
3. Replace ceiling tile by room #304 and by the football locker room.  NFPA 101: 8.4.2

WESTMEADE ELEMENTARY
2009:
1. Service emergency lights in the cafeteria nearest the kitchen.  Periodic testing is required.  NFPA 101: 7.9.3
2. Artwork shall not exceed 20% of wall space (especially Kindergarten hall).  NFPA 101: 7.9.1.1
2010/11: NONE
2011/12:
1. Service emergency lights in cafeteria and in the kitchen.  NFPA 101: 7.9.3

WHARTON ELEMENTARY
2009:
1. Classroom (and egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
2010/11: NOT AVAILABLE
2011/12: N/A

WHITES CREEK HIGH
2009:
1. Service emergency lights in the auditorium.  Periodic testing is required. NFPA 101: 7.9.3
2. Repair or replace exit signs in #184 and in the small gym.  NFPA 101: 7.10.9.1
3. Replace missing fire extinguishers outside of Auto Mechanics and by#215 and #223.  NFPA 10: 5.2.1
4. Repair stairwell door closer on lower level by #4.  NFPA 101: 7.2.1.8.1*
2010/11:
1. Repair/replace exit sign at stairway 4 (upper level).  NFPA 101: 7.2.12.3.5.2
2. Replace missing fire extinguishers (including Freshman Hall).  NFPA  10: 6.1.3
2011/12:
1. Fire alarm strobes in kitchen not working.  Repair immediately.  NFPA 101: 4.6.12.1
2. Fire doors by pool shall be repaired (fire glass broken).  NFPA 101: 8.3.4.1
3. Provide (or repair) door closers for fire door by pool by old Home Economics next to 130 and throughout.  NFPA 101: 8.4.3.5
4. Service or repair exit sign in room next to office 175, in clinic and throughout bldg.  NFPA 101: 7.10.9.1
5. Replace ceiling tile in storage room across from clinic, women's bathroom main lobby, outside gym in main lobby and throughout bldg.  NFPA 101: 8.4.2
6. There shall be no storage in stairwells.  Remove chairs, trashcans, etc.  NFPA 101: 7.2.2.5.3*
7. Dryer shall be vented to outside (old Home Economics next to 130).  NFPA 211: 10.7.3.3
8. Repair fire door so that it doesn't "stick" (hall to electronics and masonry area), outside kitchen.  NFPA 80: 2.1.4.2
9. Grills shall not be stored in bldg (ROTC).  IFC 308.3.1
10. Propane shall be stored properly (ROTC).  NFPA 30
11. Replace missing extinguishers throughout bldg.  NFPA 10: 1.5.7
12. There shall be no storage within 18 inches of sprinklers (on top of band lockers).  NFPA 13: 8.5.6.1
13. Maintain 6 feet corridor width throughout.  Relocate Coke machine by #256.  NFPA 101: 7.1.10.1*

WHITSETT ELEMENTARY
2009:
1. Emergency egress and relocation drills shall be conducted monthly and be documented.  NFPA 101: 15.7.2.1
2. Repair emergency light in gym.  Periodic testing is required.  NFPA 101: 7.9.3
3. Replace missing ceiling tile in Storage #4 and in Room #106 to limit the spread of fire and smoke.  NFPA 101: 8.3.4.1
4. Seal penetrations in gym corners (near sensors).  NFPA 101: 8.3.5.1
5. Relocate items by Room #115 to maintain exit access corridor width of not less than 6 ft (1830 mm) of clear width.  NFPA 101:  15.2.3.2
6. Maintain 18 in. or greater clearance for all storage around sprinkler heads (in Storage #4 and Storage #5).  NFPA 1: 10.19.3.2* 
2010/11:
1. Replace ceiling tile in Storage Rooms #4 and 5.  NFPA 101: 8.4.2
2. Repair storage room and HVAC door closers Throughout.  NFPA 101: 7.2.1.8
3. Fire drills shall be conducted and documented monthly.  NFPA 101: 15.7.2.2
2011/12: NONE

WRIGHT MIDDLE
2009:
1. Service emergency lights in the library by the computers, by #205, and in the gym.  Periodic testing is required.  NFPA 101: 7.9.3
2. Classroom (and egress corridor) doors shall not be propped open.  NFPA 101: 7.2.1.8.1*
3. Classrooms (including #200) shall have one outside window that remains free and clear for emergency rescue.  NFPA 101: 15.2.11.1.1
4. Computer cords in the library shall be arranged to prevent a tripping hazard.  NFPA 101: 7.1.10.1*
2010/11: NONE
2011/12:
1. Service emergency lights by room #328, in stairwell across from elevator (new wing) and throughout. Periodic testing is required.  NFPA 101: 7.9.3
2. Service fire extinguishers throughout including Class K in kitchen.  NFPA 10: 6.3.1
3. There shall be no storage in stairwells.  Remove sports equipment across from elevator in new wing.  NFPA 101: 7.2.2.5.3*
4. Kitchen suppression system shall be service every six (6) mos.  NFPA 96: 11.2.1

  • Most Popular StoriesMost Popular StoriesMore>>

  • Mom bites off dog's ear to save daughter during attack

    Mom bites off dog's ear to save daughter during attack

    Tuesday, April 22 2014 2:49 PM EDT2014-04-22 18:49:19 GMT
    Image from CNN/KHOU-TVImage from CNN/KHOU-TV
    In a backyard in Alvin, swings a very lucky girl. Her name is Mackenzi Plass, or Kenzi for short, and she survived a dog attack and has undergone several surgeries."She'll be two and a half in May," said her very proud mother Chelsi Camp. "She's doing great. You wouldn't know it if you couldn't see."Mackenzi has scars on her face after the ordeal just weeks ago that put her mother's animal instincts to the test."You do whatever you can," said Camp. "I don't have physical strength at my side."...More >>
    In a backyard in Alvin, swings a very lucky girl. Her name is Mackenzi Plass, or Kenzi for short, and she survived a dog attack and has undergone several surgeries."She'll be two and a half in May," said her very proud mother Chelsi Camp. "She's doing great. You wouldn't know it if you couldn't see."Mackenzi has scars on her face after the ordeal just weeks ago that put her mother's animal instincts to the test."You do whatever you can," said Camp. "I don't have physical strength at my side."...More >>
  • 38 dogs rescued in north Nashville dog fighting bust

    38 dogs rescued in north Nashville dog fighting bust

    Wednesday, April 23 2014 6:09 PM EDT2014-04-23 22:09:20 GMT
    A drug bust last week led to Tuesday’s seizure of 38 dogs from an alleged dog fighting ring in north Nashville.More >>
    A drug bust last week led to Tuesday’s seizure of 38 dogs from an alleged dog fighting ring in north Nashville.More >>
  • Giles County student injured, another charged in fight over gum

    Giles County student injured, another charged in fight over gum

    A Giles County middle school student is facing criminal charges and his classmate facial surgery after the two got into a fight over gum.More >>
    A Giles County middle school student is facing criminal charges and his classmate facial surgery after the two got into a fight over gum.More >>
Powered by WorldNow
All content © Copyright 2000 - 2014 WorldNow and WKRN (Young Broadcasting station). All Rights Reserved.
For more information on this site, please read our Privacy Policy and Terms of Service.